2 - Setpoint temperature display/time display "SV"
3 - Indicators RUN (unit in operation) / OUT (heating is on) / AT (AUTO function) / ALM (alarm)
4 - SET button
5 - SHIFT function button
6 - Buttons for decreasing / increasing the entered values
3.2. Preparation for operation
POSITIONING OF THE UNIT
The ambient temperature must not exceed 40°C and ambient humidity should not exceed 85%. Place the unit
in a way that ensures good air circulation. Maintain a minimum clearance of 10 cm from any wall of the unit.
Keep the unit away from any hot surfaces. Always operate the unit on a level, stable, clean, fireproof, and dry
surface and out of the reach of children and persons with impaired mental, sensory, and intellectual
functions. Place the unit in such a way that the main plug can be reached at any time. Ensure that the power
supply to the unit corresponds to that specified on the identification plate!
Before using the unit for the first time, disassemble all parts and wash them as well as the entire unit.
3.3. Working with the device
Position the device as described above.
Open the lid and add clean or distilled water to the water tank. The water level must be higher than the
heating element and the temperature sensor. CAUTION! If the error "Er-1" appears on the display, add
non-distilled water.
Connect the appropriate power supply.
The upper unit display (PV) shows the actual temperature and the lower display (SV) shows the set
temperature or time.
Press the SET button to go to the temperature setting. Set the desired temperature value using the input
decrease/increase buttons. Confirm by pressing the SET button again.
Set the desired operating time:
• Press the SET button twice.
• Use the input decrease/increase buttons to set the required time value.
• Confirm by pressing the SET button.
• The unit will start counting down when the set temperature is reached.
CAUTION! If only the temperature value is set (time value = 0), the unit will operate in continuous mode.
The AT function is designed to eliminate the possibility of control errors based on the settings of the
parameter group (proportional, integral, derivative):
Hold down the SHIFT function button for a few seconds. The "AT" indicator light will start flashing.
When finished, the "AT" indicator light will turn off and the unit will return to normal operation.
To stop the process, hold down the SHIFT function button again.
3.4. Cleaning and maintenance
a) Pull the mains plug and let the unit cool down completely before cleaning, adjusting or replacing
accessories and when the unit is not in use.
b) Use only non-corrosive cleaning agents for cleaning the surfaces.
c) After each cleaning, all parts should be thoroughly dried before the device is reused.
d) Store the unit in a dry and cool place protected from moisture and direct sunlight.
e) Do not spray the unit with a stream of water or immerse it in water.
f) Make sure that no water enters through the ventilation openings in the casing.
g) Clean the ventilation openings with a brush and compressed air.
h) Perform regular inspections of the unit checking technical fitness and any damages.