Operation and control
Automatic closing function
DANGER
Without safety devices, the automatic closing function will
also close the barrier if people or objects are underneath it.
Severe injuries and property damage may result.
¾ Install the required safety devices (photocells,
induction loops) in accordance with EN 12453.
¾ Never reach into moving parts!
¾ Keep persons and animals away from the movement
area of the barrier!
¾ Keep children away from the barrier!
¾ Always keep the moving barrier in sight!
¾ Do not pass through the barrier until it has opened
completely!
In the case of the automatic closing function, the barrier closes
automatically after a set hold open time. The hold open time is counted
down starting when the BARRIER OPEN end position is reached. If another
opening command is issued during the hold open time, the hold open time
restarts.
The barrier can be opened, but not closed with a command device.
While it is opening, the barrier cannot be stopped using a command device.
If an opening command is given again during automatic closing of the
barrier, the barrier opens completely and the hold open time restarts.
INFORMATION!
¾ The hold open time set at the factory is 30 seconds
from the end position.
¾ This value can be changed via SOMlink.
¾ The setting range for the hold open time is
10 - 120 seconds.
¾ The hold open time can be shortened to 5 seconds
after passing the photocell via SOMlink.
Setting the automatic closing function:
ON
1234
DIP switches ON OFF
1 Acactivated Deactivated
Pre-warning time
The warning light blinks during the pre-warning time to warn users of the
opening and closing of the barrier.
INFORMATION!
¾ The pre-warning time can be set separately via SOMlink
for the directions of movement OPEN and CLOSE.
¾ The setting range for the pre-warning time
is 0 - 65 seconds.
¾ The progress of the pre-warning time is displayed
by the blinking warning light.
Power-saving mode
To save energy, the control unit switches to power-saving mode after
a pre-set time.
Connected accessories, e.g. 8k2 safety contact strips or photocells,
are deactivated in power-saving mode.
With the next command via the buttons or the radio control system,
the barrier and the accessories are reactivated.
Setting power-saving mode:
ON
1234
DIP switches ON OFF
2 Deactivated Activated
Resetting the ALARM safety input
INDUC. 1 INDUC. 2 CLOCK ALARM
1. Disconnect the barrier from the mains voltage.
2. Check that it is disconnected from the voltage supply.
3. Inspect the barrier for damage and repair any damage found.
4. Reset re alarm system (close contact)
5. Restore the mains power supply
6. Execute a command using the button.