5. Commissioning
User Manual
The start and stop signal control of generator
The setting GEN Signal on App is used for control the automatic start or automatic stop of
generator .When the switch turned on, representing the generator possess the start and stop
automatically function.
When the switch turned off, representing the generator donāt have the start and stop
automatically function. Customer need to start or stop it manually by other settings.
(Tips: this function only can be used for the generator with external communication interface)
50
Backup Port Enabling Setting
Backup Port Reference Voltage Setting
Voltage Droop Setting
Min.Droop Voltage
AC Coupling Switch
With Generator
GEN Rated Power
Gen Max.Charge Power
Generator Position
GEN_Start_SOC
GEN_Exit_SOC
GEN Start Volt
GEN Exit Volt
GEN Signal
GEN Force
GEN Stop
GEN Port Load Open
Smart Load Switch
230.0V
>
180.0V
>
2.0kW
>
0.0kW
>
Grid port
>
20%
>
80%
>
46.0V
>
55.0V
>
Disable
>
Disable
>
Smart Port