5. Commissioning
User Manual
Battery Discharge Hysteresis SOC
When the Force-charge SOC is reached, the battery will be force-charged to the Overdischarge
SOC + Overdischarge Hysteresis SOC. Overdischarge Hysteresis SOC range from 1% to 20%,
Overdischarge Hysteresis SOC default value is 1%.
For example: If customer set the Overdischarge SOC is 20%, Overdischarge Hysteresis SOC
is 5%.When the battery SOC is discharged to 10%( Forcecharge SOC set as 10%), Then the
lithium SOC will be forcecharged to 25%.
Battery Healing function
When the lithium battery is kept at low SOC for a long time, the measurement of lithium battery
SOC is not accurate. The Battery Healing function will allow the system to charge the battery to
the set Battery Healing SOC when the battery reaches the discharged SOC, so as to ensure the
healthy and stable operation of the lithium battery.
The Battery Equalization function of lead-acid battery
Pre-condition: When the days since last battery balancing exceed battery balancing Interval
days already set.Then the inverter will not enter the floating charge mode when the lead-acid
battery floating charge judgment is met for the first time on the same day when pre-condition
occur. But force charge battery at a balanced voltage on a constant voltage state, the charging
time is the time of balance, after finishing it, battery enter into float-charging state.
46
Battery Type
Battery Model
Max Charging Current
Max Discharging Current
Overdischarge SOC
Overdischarge Hysteresis SOC
Forcecharge SOC
Battery Healing Switch
Battery Healing SOC
Peak-shaving Setting
Max.grid power when Force charging
ECO Function
Battery Wakeup Switch
Auto Bat Awaken
Lithium Battery
>
Lithium Battery LV(RS485)
>
190.0A
>
190.0A
>
20%
>
1%
>
10%
>
100%
>
5000W
>
Battery Type
Battery Capacity
Max Charging Current
Max Discharging Current
Overdischarge Voltage
Forcecharge Voltage
Float Voltage
Temperature compensation coefficient
Battery Equalization
Equal Time
Equalized Interval
Peak-shaving Setting
Bulk Voltage
Equalization Voltage
Max.grid power when Force charging
ECO Function
Battery Wakeup Switch
Auto Bat Awaken
Lead-acid Battery
>
200Ah
>
50.0A
>
50.0A
>
44.5V
>
43.8V
>
57.6V
>
54.0V
>
0mV/°C
>
55.0V
>
180min
>
30day
>
1000W
>
Battery Setting
Battery Setting