Visibility of the LED indicator lights should be considered.
Adequate ventilation around the inverter must be provided.
NOTE
Nothing should be stored on the top of or placed against the inverter.
The inverter must be mounted vertically with a maximum incline of +/- 5 degree.
Exceeding this may cause the output power to derate.
Figure 3.4 Inverter Mounting Clearances
Mount the inverter on a wall or structure capable of bearing the weight of the machine.
3.3 Mounting the Inverter
User Manual
3. Installation
To avoid overheating, always make sure the flow of air around the inverter is not
blocked. A minimum clearance of 500mm should be kept between inverters or
objects and 1000mm clearance between the bottom of the machine and the ground.
≥500mm
≥500mm
≥500mm
≥1000mm
≥1200mm
11