5. Commissioning
User Manual
Parallel Setting
Parallel Mode: Single/Parallel
Address ID: 1 to 6
Manual Set Master/Slave: Address ID 1 is Master, the others is Slave.
Inverter Connected Phase Setting: Single Phase(single phase system)/
Phase A(Three Phase)/Phase B(Three Phase)/Phase C(Three Phase)
Total number of hybrid inverters connected: 0-6
Parallel Sync: The parameters of the master will be synchronized to the slaves, and some
parameters of the slave cannot be set.
Parallel Setting
Parallel Mode
Single >
Address ID
2 >
Manual Set Master/Slave
Slave >
Inverter Connected Phase Setting
Single Ph... >
Battery Rated Energy Setting
3.0kWh >
Total number of hybrid inverters connected
2 >
Parallel Sync
The inverter commissioning process has now been completed. It is recommended to monitor
the system closely over the next week to ensure that everything is working as it should.
Please refer to the Solis data logger manual for assistance with registering a new plant on
SolisCloud.
NOTE:
A full factory reset can be done, if needed. This function can be found in the
Special Setting Function menu within the Settings tab.
51