5. Commissioning
User Manual
Meter/CT Setting
You can select meter or CT for system measurement.
Meter Type: Please select a correct type. The wrong option may cause the meter RS485
communication Failed. If the battery and meter are not connected, please select the
ā€œNO Meterā€ to shield the alarm of meter communication fault.
CT Reverse: If the direction is wrong, the sampling current of CT will be reversed when
calculating the power.
CT Ratio: CT ratio is adjustable.
Meter/CT Setting
Meter/CT Setting
Meter >
Meter Setting
>
Meter/CT Setting
Meter/CT Setting
CT >
CT Reverse
Forward >
CT Ratio
10 >
Grid Power Setting
System Export Power/Current: This is the amount of power/current the inverter is permitted
to export(or sell) back to the utility company. If you do not want the system exporting power,
this setting must be configured.
Failsafe Switch: Enabling the Failsafe switch will mean that the inverter will not produce any
P power if the inverter loses communication with the meter.
Grid Power Setting
System Export Power Limit Switch
System Export Power Limit Value
0W >
System Export Current Limit Value
0.0A >
Failsafe Switch
Backup Setting
Backup Voltage Setting: This is the voltage designated to the backup loads in the event of
a grid power loss.
Backup Setting
Backup Port Enabling Setting
Backup Port Reference Voltage Setting
230.0V >
Voltage Droop Setting
47