Adjustment to work in airfl ow mode
The selection between pressure and airfl ow is made by the DIP3(SW1) micro switch existing inside
the micro switch. Fix the micro switch in ON position.
Indicate the airfl ow range
Once confi gured the airfl ow measurement, press the “OK” button to set the fi rst digit of factor k. The
value fl ashes and is adjusted using the buttons “” and “”. When set, press the “OK” button to
memorise the factor k. The actual measured value is displayed. If an airfl ow range is selected it is
not necessary to enter a range of pressures.
Model K factor
UVF-400/160 ECOWATT 20
UVF-600/200 ECOWATT 47
UVF-1100/250 ECOWATT 55
UVF-1500/315 ECOWATT 84
UVF-2500/355 ECOWATT 110
UVF-3000/400 ECOWATT 105