To activate the Free Cooling Night function it is necessary to acces as adminstrator.
1- Access to system level
2- Activate the free cooling function and defi ne the setpoint temperature
Manual/Auto
Sengs
Configuraon
Access Rights
In/out
Sengs sensor
Funcon control
Fan control
Change
parameters
Confirm
the changes
Modify the value
15. WATER HEATER FROST PROTECTION
In models with Water Heater, the temperature of the water return is continually supervised
by a probe, in order to prevent it to freeze.
In case water temperature drops below 12°C, the water valve starts to open (if it already
wasn’t) and
Frost Risk
alarm is activated.
If water temperature falls below 7°C, then fans are stopped and the alarm
Water temp too
low, system off
is activated. Till the temperature is not over 7°C, the unit will not turn on
again.
Unit in OFF mode
When the unit is OFF, antifrost protection remains active trying to maintain a constant re-
turn water temperature of 25°C.