The instructions in current regulations regarding the protection of electrical lines
against defects and direct and indirect contact must be obeyed at all times.
After these steps are performed, check to make sure all electrical connections
are secure (loose wiring connections can cause irreparable damage).
Check to make sure the electrical resistance between earth and any electrical
terminal is greater than 1 megohms. If it is not, do not start up the unit until the
electrical short has been located and repaired.
As a safety measure, if there is no power to the fan, the necessary interlocks must
be performed so that all other electrical components are also de-energised.
7.11. TEMPERATURE PROBES LOCATION
The UTBS-PRO-REG units are with the air temperature probes wired to the electrical board.
All the versions include 3 different temperature probes to manage air heating and/or coo-
ling demand:
- T
SUP
: Supply air temperature. Mounted at the UTBS module air outlet. Factory wired, this
probe is used to control the supply air temperature. This sensor should not be manipulated.
- T
ODA
: Outdoor air temperature. This probe is delivered inside the electric cabinet (coiled
itself). Although the probe is factory wired to the PCB controller, the installer must fi t the
sensor inside the duct system depending on the type of installation performed.
- T
ETA
: Extract air temperature. This probe is delivered inside the electric cabinet (coiled
itself). Although the probe is factory wired to the PCB controller, the installer must fi t the
sensor inside the duct system depending on the type of installation performed.
Outdoor air (ODA) and Extract air (ETA) temperature probes are 4m lengh, allowing that
each probe will be mounted in the desired position.
IMPORTANT: Regardless of the type of installation performed, the three air probes must
always be wired to the control cabinet. If any of the temperature probes is missing, it will
cause the unit malfunction as well as the alarm message on the controller display.
During the unit installation, the installer should retire the temperature probes from into
the electrical cabinet and fi t them in the defi nitive position according depending on the
operation mode.
Detail of the location of the Outdoor Air temperature probe (T
ODA
) and the Extract Air tem-
perature (T
ETA
) depending on the type of installation:
The unit installation must meet the following regulations:
- Low Voltage Directive 2006/95/CE
- Machinary Directive 2006/42/CE
- Electromagnetic Compatibility 2004/108/CE