Without display With display
Register set point 0 Pressure (Pa) Register set point 0 Pressure (Pa)
1 000 100 100 160
2 000 300 200 320
3 000 500 300 480
4 000 700 400 640
4 500 800 500 800
4 500 à 10 000 800 600 960
700 1 120
800 1 280
900 1 440
1000 1 600
6. MAINTENANCE
The maintenance frequency depends on the operating conditions. If the air is highly loaded with impurities,
the duration between two visits must be shortened.
WARNING: Before any maintenance operation, cut off the power supply upstream of the casing and make
sure that it cannot be re-established during the intervention (lockout).
The motors used do not require any particular maintenance. They are fi tted with sealed greased-for-life
ball bearings.
Perform a periodical check based on the following indications:
Unit/Item At commissioning Every 6 months minimum
Turbine
Check the direction of rotation and the absence
of friction between the moving parts and the fi xed
parts
Clean if necessary, check the absence of
friction between the moving parts and the
fi xed parts
Controller Check the connections, especially those to earth
Retighten the terminals if necessary, check
the rated current
Switch Check the connections, especially those to earth Tighten the terminals if necessary
Protective grilles Check the presence Clean if necessary
Duct networks Check the sealing Clean if necessary
Fastenings Check the tightness Tighten the screws if necessary
Pressure tapping Check the aeraulic connections Check the operation