HXBR-ECOWATT
1
2
3
IN110V D0D1D0D1
GND
FG
24VENIN224V
OUT
NC
NO
NL
J5
J6
GND GND GND COM
F1
Terminal Function/Technical specifi cation
L, N, Ground Supply voltage 230V±10% 50/60Hz
NO Status relay, open with internal error and/or motor stopped
COM Status relay, shared connection (2A, 30VDC / 230VAC)
NC Status relay, closed with internal error and/or motor stopped
24V, EN Remote ON/OFF; bridge between terminals, motor ON; by default from factory
GND Ground reference for control
IN2 Sensor input, 0-10V or 4-20mA
24V Voltage output, 24VDC (100mA)
OUT Slave output, 0-10V (5mA)
D0 Modbus RTU (RS485)
D1 Modbus RTU (RS485)
FG Hall Output (1 pulse/rev.)
IN1 0-10V / 4-20mA / PWM
10V +10VDC (10mA)
Jumper Function/Technical specifi cation
J5.1 Selection of input IN1, 0-10V/4-20mA sensor, open by default (0-10V)
J5.2 Selection of input IN2, 0-10V/4-20mA sensor, open by default (0-10V)
J5.3 Final selection Modbus network, open by default
J6 Selection of internal tachometer output (referenced to 10V), open by default
Fuse Function/Technical specifi cation
F1 Final protection against general failure of electronic protections (5x20, 10A Fast)