17
3 Production Information
Module T-BAT HS28.8 T-BAT HS32.4 T-BAT HS36.0 T-BAT HS39.6 T-BAT HS43.2 T-BAT HS46.8
Nominal Voltage (Vdc) 409.6 460.8 512 563.2 614.4 665.6
Operating Voltage (Vdc) 360-465 450-522 450-480 495-636 540-695 585-750
Nominal Capacity (Ah) 72 72 72 72 72 72
Nominal Energy (kWh) 29.49 33.18 36.86 40.55 44.24 47.92
Usable Energy 90% DOD
(kWh)
26.5 29.9 33.2 36.5 39.8 43.1
Max. Charge/Discharge
Current (A)
50 50 50 50 50 50
Recommend Charge/
Discharge Current (A)
50 50 50 50 50 50
Standard Power (kW) 14.34 16.13 17.92 19.71 21.50 23.30
Max. Power (kW) 20.48 23.04 25.6 28.16 30.72 33.28
Short-circuit Current (A) 1850 1850 1850 1850 1850 1850
Battery Round-trip
Efficiency (0.2 C, 25°C)
95%
Expected Lifetime (25°C
)
10 years
Cycle Life 90% DOD
(25°C)
6000 cycles
Charge Temperature -30°C ~ 53°C (on heating function); 0°C ~ 53°C (off heating function)
Discharge Temperature -30°C ~ 53°C (on heating function); -20°C ~ 53°C (off heating function)
Storage Temperature
-20°C ~ 53°C (3 months)
10°C ~ 40°C (1 year)
Ingress Protection IP65
Protection Class I
*Note:
1.
Test conditions: 100% DOD, 0.2 C charge & discharge @ +25°C.
2.
90% DOD; System usable energy may vary with inverter different setting.
3.
Discharge: In case of battery cell’s temperature range of -20°C~10°C and
45°C~53°C, the discharge current will be reduced; Charge: In case of battery
cell’s temperature range of 0°C~25°C and 45°C~53°C, the charge current
will be reduced. Product charge or discharge power depends on the actual
temperature of battery pack.
4.
The battery can only be discharged and cannot be charged at the range of
from -20°C to 0°C.
5.
In case of a rated current of 30 A, the wire size of 5.5-6.5 mm² for cables
(including grounding cable) is recommended; in case of a rated current of
45 A, the wire size of 8.5-9.5 mm² for cables (including grounding cable) is
recommend.
6.
In the allowable range, the relative humidity range should be between 5%
and 95% RH. In the meantime, effective measures should be taken to prevent
condensation.