7/13
Building Technologies Division CC1N7130en
Infrastructure & Cities Sector 22.08.2013
Technical data (cont´d)
Detector current
required
(with flame)
Perm. detector
current
(without flame)
Possible detector current
with flame
(typically)
QRB... ¹)
Min. 45 µA
Max. 5.5 µA
100 µA
QRC... ¹)
Min. 45 µA
Max. 5.5 µA
70 µA
Detector current in operation:
- Flame signal instable
- Green LED flashing
Detector current in operation:
- Flame signal stable
- Green LED steady on
QRB...
¹) <45 µA >45 µA
QRC... ¹)
<45 µA
>45 µA
¹) The values given in the table above only apply under the following conditions:
- Mains voltage depending on execution AC 120 V or AC 230 V
- Ambient temperature 23 °C
Q
RB...
QRC...
12
11
LMO...
bl
µA DC
+
QRB...
7130v01/0700
sw
12
11
LMO...
1
swbl
br
µA DC
+
QRC1...
7130v02/0700
Legend
µ
A DC DC microammeter
with an internal
resistance of
Ri = max. 5 k
bl Blue
sw Black
br Brown
A
s an alternative to detector current measurement, the Interface OCI400 / with PC
software ACS400 / ACS410 can be used. In that case, the DC microammeter is not
required.
Flame supervision with
QRB... or QRC...
Green LED for
operational status
indication
Measuring circuit
for detector current