A Series Water and Remote User Manual
November 2020
Page 8
Remote condenser models have additional installation
needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of
the ice machine cabinet. Tubing kits are available in
several lengths to accommodate most installations.
Order the one that just exceeds the length needed for
the installation.
The kit numbers are:
BRTE10, BRTE25, BRTE40, BRTE75
There are limits as to how far away from the ice
machine and where the remote condenser can be
located. See page 9 for those limits.
The correct condenser must be used:
Ice Machine
Model
Voltage Condenser
Model
NH2030R-32
NS2030R-32
FS2330R-32
NH2030R-3
NS2030R-3
FS2330R-3
208-230 ER6111-32
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will
cause compressor failure and will void the warranty.
A headmaster is required for all remote condenser
systems. Installation of headmaster kit KPFHM will be
required if any of the following condensers are being
used:
ERC101-1, ERC151-32, ERC201-32, ERC301-32,
ERC402-32
Use of non-Scotsman condensers requires
pre-approval from Scotsman Engineering.
Refrigeration - Remote Condenser Models