32 Perform a compressor test
16. Perform a compressor test
The compressor test function allows to check that the compressor of the refrigeration system is operating correctly
(depending on the inlet and outlet temperatures).
Three temperature probes are needed to perform this measurement. Minimum one Si-RT7 will be necessary.
T3 is the discharge line temperature (DLT).
10:09 Menu
Measurements / Tests
Measurement settings
Wireless connection
General settings
Fault tree analysis
Data recording
Device information
>
>
>
>
>
>
>
10:09 Measurements / Tests
10:09
Auto-Detection
LP
HP
T1
T2
T3
Sensor auto-detection in progress...
Internal 1
Internal 2
Wired Port 1
Wired port 2
...
10:09
Comp. - R134a
LP
3.63
-1.00
10.00bar -1.00 28.00bar
HP
12.69
1
EV
T1
SH
13.2 °C
23.6 °C
3.0 °C
CO
T2
[075]
SC
T3
51.5 °C
24.9 °C
26.6 °C
95.5 °C
10:09
Auto-Detection
Sensor auto-detection complete.
1
LP
HP
T1
T2
T3
Internal 1
Internal 2
Wired Port 1
Wired port 2
[075]
>
>
>
>
Target superheat
Delta T
Compressor test
Efciency (COP / CER)
Before each test it is recommended to zero the pressure sensors in ambient pressure, before connecting
hoses.
It is only possible to zero pressure with less than 0.3 bar pressure measured, to avoid accidental zero.
"Measurements / Tests" menu is displayed.
• Press OK on "Compressor test" line.
• Press OK once the manifold has complete the auto-detection.
• Perform an autozero by pressing
for 3 seconds.
Results are displayed on the manifold screen.