28 Modbus
13. Modbus
13.1 Conguration of parameters
• Communication speed: between 2400 and 115200 bauds, 9600 bauds by default
• Data bits: 8 bits
• Stop bit: 1 bit
• Parity: None
• Flow control: None
• Transmitter addressing: between 1 and 255 (automatically answers the requests from address 0)
• Data sending: made by words of 2 bytes, in the following order most-signicant then least-signicant byte
13.2 Functions
• Register function: Function 03
• Register writing: Function 16
• Communication loop test: Function 08
13.3 Data format
UNIT8 Byte 1 Byte 0 (lsb)
Value (0x01) 0x00 0x01
Registers
Reg0
0x00 0x01
UNIT16 Byte 1 Byte 0 (lsb)
Value (0x0102) 0x01 0x02
Registers
Reg0
0x01 0x02
UNIT32 Byte3 Byte2 Byte1 Byte0 (lsb)
Value (0x01020304) 0x01 0x02 0x03 0x04
Registers
Reg0 Reg1
0x03 0x04 0x01 0x02
FLOAT32 Byte3 Byte2 Byte1 Byte0 (lsb)
Value (0x01020304) 0x01 0x02 0x03 0x04
Registers
Reg0 Reg1
0x03 0x04 0x01 0x02
13.4 Enumeration table
13.4.1 Languages enumeration
Identier Language
0 English
1 French
2 Spanish
3 Italian
4 German
5 Portuguese
6 Chinese
7 Dutch