The SI1800, Si-82 or SI-1801centrifugal monobloc pumps are designed for use with all kinds of Air conditio-
ning units, refrigeration display cabinets, fan coil units and gas condensing boilers. They can also be used
with gas red furnaces. The pump can be used to remove acid condensates (pH > 2.5) and condensates
with a temperature of up to 65°C.
Vertical
discharge
head
Total tubing length
5 m 10 m 20 m 30 m
1 m 380 300 240 190
2 m 310 260 200 150
3 m 240 200 145 110
4 m 150 130 80 60
5 m 30 20 0 0
The head losses dened in this table are calculated with
a Ø 10 mm int. hose.
EN
Vertical
discharge
head
Total tubing length @ 50 / 60 Hz
16 ft
(5 m)
30ft
(10 m)
60ft
(20 m)
100ft
(30 m)
3 1/4ft (1 m) 100 92 74 61
6 1/2ft (2 m) 82 75 61 50
10ft (3 m) 65 58 48 38
13ft (4 m) 50 42 36 28
16ft (4.9 m) 30 /37 26 /29 21 /22 16 /17
18ft (5.5 m) 11 /20 8 /13 5 /11
Actual ow rates (l/h)
Mains supply
230V~ 50Hz - 70 W - 0.67 A
Safety switch NC 4 A resistive - 250V
Max. ow rate 500 l/h
Max. discharge head 5.0 m
Operating time S3: 30% (3 s ON – 7s OFF)
Noise level in application 45 dBA at 1 m (3.3 ft)
Water levels (mm) Fig. 4
Max. condensate tempera-
ture & acidity
t<65°C (80°C - 1min),
pH>2.5
Tank volume 2.0 l
Thermal protection
(overheat)
105°C (auto-reset)
Protection IP 20
WARNING
- This pump has been designed for use with water only.
- This pump has been designed for indoor use only. It must not
be immersed and/or placed in areas of high humidity or where
the ambient temperature conditions are below freezing.
- The appliance is not to be used by children or persons with
reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given
supervision or instruction.
- Children should be properly supervised to ensure they do not play with the appliance.
- In case of breakdown, in particular if the supply cord is damaged, it must be replaced by a Sauermann
service agent or a similarly qualied person in order to avoid any hazard.
- For models tted with a supply cord without a plug, a means for disconnection must be incorporated to the
xed wiring in accordance with local wiring rules.
- The pump shall not be installed in air handling spaces (such as a plenums or the airhandling compartment
of a condensing unit).
Technical specication : SI82CE01UN23 - SI82CE02UN23
- SI1800SCUN23 - SI1802CUN23 - SI1802SCAN23
17’ 23’
Mains supply 120V~60Hz
230V~50/60Hz
56W - 1.05 A (5)
85W - 1.45 A
(1) (3)
80 W - 0.72 A
(2) (4)
Safety switch
NC 4 A resistive - 42 V peak
Max. ow rate
132 gph (500 l/h)
Max. discharge 60Hz
head 50Hz
16’ (4.9m) 21’ (6.4m)
18’ (5.5m)
Operating time
S3: 30% (3 s ON – 7s OFF)
Noise level in application
45 dBA at 3.3 ft (1 m)
Water levels (mm)
Fig. 4
Max. condensate
temperature & acidity
t<150°F - 65°C, 1 min
pH>2.5
Tank volume
1/2 US Gal (2.0 l)
Thermal protection
(overheat)
230 F° (110°C)
auto-reset
248°F (120°C)
auto-reset
Protection IP 20
Technical specication : 17’ : SI1801LHUS11 (5)
23’ : SI1801SCUS11 (1) - SI1801SCUS23 (2) - SI1801US11/T (3) -
SI1801US23/T (4)
The head losses dened in this table are calculated with
a Ø 1/4’’ (10 mm) int. hose.
Actual ow rates (gph)
EN
Vertical
discharge
head
Total tubing length @ 60 Hz
16 ft
(5 m)
30ft
(10 m)
60ft
(20 m)
100ft
(30 m)
3 1/4ft (1 m) 92 82 63 53
6 1/2ft (2 m) 79 69 53 44
10ft (3 m) 61 52 40 33
13ft (4 m) 40 32 26 21
16ft (4.9 m) 13
23’
17’
N921-06_2012.indd 8N921-06_2012.indd 8 19/03/2020 11:58:3319/03/2020 11:58:33