Press OK when the last digit has been set to validate the diameter.
9.4.4 Set the airow coefcient (CP210-R)
This function is available on CP210-R with SQR3 option only.
This coefcient allows to calculate an airow from the pressure. It is indicated by the manufacturer that supplies air vents
with pressure connections (+ and -). From the square root of the measured pressure (Delta P), and this coefcient, you will
get the airow:
Airflow=C
D
Δ pressure
The transmitter is powered on.
Press OK.
Enter the activation code (see page 8).
Press OK.
Press Up key to go to “F 625” folder to set the coefcient value.
Press OK.
Set the coefcient with Up and Down keys.
Press OK when the last digit has been set to validate the coefcient.
This coefcient must be between 0000.0 and 9999.9.
Press Up key to go to “F 626” folder to set the unit of measurement.
Press OK.
Select 0, 1, 2, 3 or 4 for:
0: Pa
1: mmH
2
O
2: inWG
3: mbar
4: mmHG