hysteresis of the alarm 1
F 404 U16 4040 Delay-time 1 setting of the
alarm 1
From 0 to 600 s
F 405 U16 4050 Delay-time 2 setting of the
alarm 1
From 0 to 600 s
F 406 Boolean 4080 Audible alarm 1 1: activated / 0: deactivated
F 407 U8 4070 Alarm 1 acknowledgement
duration
From 0 to 60 minutes
F 410 Enumeration 4100 Alarm mode of the alarm 2 0: None
1: Rising edge
2: Falling edge
3: Monitoring
F 411 U8 4110 Channel selection alarm 2 Channel 1
Channel 2
Channel 3
F 412 Real 4120 Threshold 1 setting of the
alarm 2
According to the connected probe
F 413 Real 4130 Threshold 2 setting or
hysteresis of the alarm 2
According to the connected probe
F 414 U16 4140 Delay-time 1 setting of the
alarm 2
From 0 to 600 s
F 415 U16 4150 Delay-time 2 setting of the
alarm 2
From 0 to 600 s
F 416 Boolean 4180 Audible alarm 2 1: activated / 0: deactivated
F 417 U8 4070 Alarm 2 acknowledgement
duration
From 0 to 60 minutes
F 420 Enumeration 4200 Alarm mode of the alarm 3 0: None
1: Rising edge
2: Falling edge
3: Monitoring
F 421 U8 4210 Channel selection alarm 3 Channel 1
Channel 2
Channel 3
F 422 Real 4220 Threshold 1 setting of the
alarm 3
According to the connected probe
F 423 Real 4230 Threshold 2 setting or
hysteresis of the alarm 3
According to the connected probe
F 424 U16 4240 Delay-time 1 setting of the
alarm 3
From 0 to 600 s
F 425 U16 4250 Delay-time 2 setting of the
alarm 3
From 0 to 600 s
F 426 Boolean 4280 Audible Alarm 3 1: activated / 0: deactivated
F 427 U8 4070 Alarm 3 acknowledgement
duration
From 0 to 60 minutes