Sauermann CP 115 handleiding

36 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 6 van 36
Standard range / central zero setting – left DIP switch
Please follow carefully the combinations beside
with the DIP switch. If the combination is wrongly
done, the following message will appear on the display
of the transmitter “CONF ERROR”. In that case, you will
have to unplug the transmitter, place the DIP switches
correctly, and then power the transmitter up.
Output setting – right DIP switch
(CP 111/112/113/114/115 – AO and CP 111/112/113 – AN models)
To set the type of analogue output, please put the on-off
switch of the output as shown beside.
Units setting – right DIP switch
To set a measurement unit, put the on-off switches 2, 3 and 4 of the units as shown in the table below.
Congurations Full scale Central zero
Combinaisons
Example:
• 0 - 100 Pa: Full scale / 0
Central zero
(0 / 100 Pa)
(-50 Pa / 0 / +50 Pa)
Congurations 4-20 mA 0-10 V
Combinations
1
2
3
4
1
2
3
4
Example:
• From 0 to 750 mmH
2
O, measuring range is 750 mmH
2
O.
• From -500 mbar to +500 mbar, measuring range is 1000 mbar.
• Measuring ranges of the CP114 transmitter on the ±500 mbar range according to the measurement unit.
• Measuring ranges of the CP115 transmitter on the ±2000 mbar range according to the measurement unit.
Combination 1 Combination 2 Combination 3 Combination 4 Combination 5
Type of transmitter CP114 CP115 CP114 CP115 CP114 CP115 CP114 CP115 CP114 CP115
mbar 100 500 200 750 300 1 000 400 1 500 500 2 000
inWG 40.0 200.0 80.0 300.0 120.0 400.0 160.0 600.0 200.0 800.0
kPa 10.0 50.0 20.0 75.0 30.0 100.0 40.0 150.0 50.0 200.0
PSI 2.0 10.0 4.0 15.0 6.0 20.0 8.0 30.0 10.0 40.0
mmHg 80 400 160 600 240 800 320 1 200 400 1 600
mmH
2
O 1 000 5 000 2 000 7 500 3 000 10 000 4 000 15 000 5 000 20 000
daPa 1.0 5.0 2.0 7.5 3.0 10.0 4.0 15.0 5.0 20.0
hPa 100 500 200 750 300 1 000 400 1 500 500 2 000
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Congurations Pa mmH
2
O mbar InWG mmHG daPa kPa hPa
Combinations
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
CP 114, CP 115
CP 111, CP 112, CP 113
Congurations mbar inWG kPa PSI mmHG mmH
2
O daPa hPa
Combinations
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
CP 114, CP 115

Bekijk gratis de handleiding van Sauermann CP 115, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSauermann
ModelCP 115
CategorieNiet gecategoriseerd
TaalNederlands
Grootte6528 MB