Units setting – right DIP switch
To set a measurement unit, put the on-off switches 2, 3 and 4 of the units as shown in the table below.
Congurations Full scale Central zero
Combinaisons
(0 / 100 Pa)
(-50 Pa / 0 / +50 Pa)
Congurations 4-20 mA 0-10 V
Combinations
Conguration via LCC-S software (option)
An easy and friendly conguration with the software!
You can congure your own intermediary ranges.
The minimum difference between the high range and the
low range is 20.
For example, it is possible to set the instrument from -20 to 0 Pa, from
0 to +20 Pa, or from -10 to +10 Pa...
To access the conguration via software: set the DIP switches as
shown beside.
Note: the on-off switch 1 of the right DIP switch can be in any position
(selection of the analogue output 0-10V or 4-20 mA).
Connect the cable of the LCC-S to the connection of the transmitter.
The conguration of the parameters can be done either
with the DIP switch or via software (you cannot combine both
solutions).
Mounting
To mount the transmitter, mount the ABS plate on the wall (drilling:
Ø6mm, screws and pins are supplied).
Insert the transmitter on the xing plate (see A on the drawing
beside). Rotate the housing in clockwise direction until you hear a
“click” which conrms that the transmitter is correctly installed.
Once the transmitter is installed and powered up, please
make an autozero to guarantee the correct working of the
transmitter in any position.
Accessories
Maintenance: please avoid any aggressive
solvent. Please protect the transmitter
and its probes from any cleaning product
containing formalin, that may be used for
cleaning rooms or ducts.
Precautions for use: please always use the device
in accordance with its intended use and within
parameters described in the technical features in order
not to compromise the protection ensured by the
device.
7.5 mm
8 mm
4.5 mm
40 mm
50 mm
68 mm
75 mm
37.5 mm
23.75 mm
14 mm
A
A
Refer to the user manual of the
LCC-S to make the conguration.
Conguration via PC
1
2
3
4
1
2
3
4
Left DIP switch Right DIP switch
Please refer to the data sheet to get more information about available accessories.