23
ENGLISH
3. If you cannot charge the refrigerant according to the upper steps, following these :
1) Open both liquid stop valve and gas stop valve.
2) Operate the air conditioner by pressing the K2 key on the outdoor unit PCB.
3) About 30 minutes later, charge the refrigerant through the service port of g
as stop valve.
• If necessary, refer to the pressure table classied by outdoor temperature.
NOTE
1
Ref.
Gas side stop valve(service port)
Outdoor unit
Indoor unit
Balance Vacuum pump
Liquid side stop valve(service port)
Important information regulation regarding the refrigerant used
This product contains uorinated greenhouse gases. Do not vent gases into the atmosphere.
• Inform user if system contains 5 tCO₂e or more of uorinated greenhouse gases. In this case, it has to be checked
for leakage at least once every 12 months, according to regulation n°517/2014. This activity has to be covered by
qualied personnel only.
• In case situation above (5 tCO₂e or more of R-410A), installer (or recognized person which has responsibility for
nal check) has to provide a maintenance book, with all the information recorded according to REGULATION
(EU) No 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on uorinated
greenhouse gases.
CAUTION
Please ll in the following with indelible ink on the refrigerant charge label
supplied with this product and on this manual.
① : The factory refrigerant charge of the product.
② : The additional refrigerant amount charged in the eld.
① + ② : The total refrigerant charge.
a. Factory refrigerant charge of the product: see unit name plate
b. Additional refrigerant amount charged in the eld(Refer to the
above information for the quantity of refrigerant replenishment.)
c. Total refrigerant charge
d. Refrigerant cylinder and manifold for charging
NOTE
The lled-out label must be adhered in the proximity of the product charging
port (e.g. onto the inside of the stop valve cover).
Refrigerant type GWP value
R-410A 2088
GWP=Global Warming Potential
Calculating tCO₂e : kg x GWP / 1000
Indoor unit
d
②
①
Unit
kg tCO2e
①, a
②, b
①+②, C
CAC GD-EU_IM_32793A-23_EN.indd 23 2016-05-25 오후 7:08:42