Samsung RC140PHXEA handleiding

66 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 66
21
ENGLISH
Connecting the refrigerant pipe
Refrigerant piping system
Items
Maximum allowable length
Single installation DPM installation
Applicable outdoor unit models
AC090FCAEH
AC100FCADH
AC100FCASEH
RC090HXEA
RC100DHXA
RC100SHXEA
AC071HCAPKH
AC090HCADH
AC100HCADH
AC120HCADH
AC100JXADH
AC120JXADH
AC100JXADEH1
AC100FCAPH
AC100FCAFH
RC100PHXA
RC100ZHXEA
RC100DHXEH
RC100DHXEG
RC125HX
RC140HX
RC155DHXEH
RC155DHXEG
RC180DHXGH
RC180DHXGG
AC090HCAPKH
AC100HCAPH
AC120HCAPH
AC140HCAPH
AC140HCADH
AC140JXADH
AC100FCADH
RC100DHXA
AC100HCADH
AC120HCADH
AC100FCAPH
RC100PHXA
RC125DHXEB
RC125DHXGA
RC125PHXA
RC140DHXEB
RC140DHXGA
RC140PHXA
AC140HCADH
Total pipe length (L
1
+…+L
n
+1+a+b) - - 50 m 75 m
Main pipe (L
1
) 50 m 75 m 30 m 50 m
Max. distance among indoor units (D) - - 10 m 10 m
Max. length after branch - - 15 m 15 m
Max. height dierence between outdoor and indoor units (h
1
) 30 m 30 m 30 m 30 m
Max. height dierence among indoor units(h
2
) - - 0.5 m 0.5 m
Max Pipe length dierence among indoor units after branch
[L
2
-L
3
or L
2
-L
4
or L
2
-L
5
or a-b or (a+L
2
)-(b+L
4
) or (a+L
3
)-(b+L
5
)]
- - 5 m 5 m
"n" means the number of indoor unit connection of DPM.
indoor
indoor
indoor
outdoor
outdoor
outdoor
indoor
indoor
indoor
indoor
indoor
indoor
indoor
outdoor
L
1
L
1
L
2
L
2
D
D
D
D
h
2
h
2
L
3
L
3
L
4
L
4
L
5
L
1
a
b
D
L
1
L
2
L
3
h
1
h
2
h
1
h
1
h
1
n=1
n=2
n=3
n=4
Use a joint kit that is only for DPM.
CAC GD-EU_IM_32793A-23_EN.indd 21 2016-05-25 오후 7:08:28

Bekijk gratis de handleiding van Samsung RC140PHXEA, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSamsung
ModelRC140PHXEA
CategorieAirco
TaalNederlands
Grootte7101 MB