Samsung MCU-4EAE1 handleiding
Handleiding
Je bekijkt pagina 19 van 24

19
ENGLISH
Installing the wire
Supply the 220-240V power to L, N of MCU separately with outdoor unit.
Connect the communication cable from the outdoor unit to F1, F2 of MCU.
Power Line and communication line must be connected as shown in drawing.
Input socket
Choose the compressed socket based on the cross-section of the connecting wire.
Case 1
Indoor
Unit
Indoor
Unit
Outdoor
Unit
ELB
MCCB
220-240V
(Supply separately)
Case 2
Indoor
Unit
Indoor
Unit
Outdoor
Unit
ELB
MCCB
220-240V
(Supply separately)
Silver solder
Norminal
dimensions for
cable (mm
2
)
Norminal
dimensions for
screw (mm)
B D d1 E F L d2 t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min. Min. Max.
Standard
dimension
(mm)
Allowance
(mm)
Min.
1.5
4 6.6
±0.2 3.4
+0.3
-0.2
1.7 ±0.2 4.1 6 16 4.3
+0.2
0
0.7
4 8
2.5
4 6.6
±0.2 4.2
+0.3
-0.2
2.3 ±0.2 6 6 17.5 4.3
+0.2
0
0.8
4 8.5
4 4 9.5 ±0.2 5.6
+0.3
-0.2
3.4 ±0.2 6 5 20 4.3
+0.2
0
0.9
Bekijk gratis de handleiding van Samsung MCU-4EAE1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.