Samsung AM200AXVFNH handleiding

62 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 18 van 62
18
Refrigerant pipe installation
English
Installation Procedure
Amount of additional refrigerant for each indoor unit ( )
(Unit: kg)
Capacity (kW)
Model
1.5 1.7 2.2 2.8 3.6 4.5 5.6 6 7.1 8.2 9 9.3 11.2 12.8 14 16 18 22 22.4 28 32 50
500
CMH
1000
CMH
Slim 1way cassette (JSF)
(AM****N1DEH*)
0.25 0.25 0.25 0.32 0.32
Interior 1way cassette
(AM***HN1DEH*)
(AM***NN1PEH*)
0.15 0.15
2way cassette
(AM***FN2DEH*)
0.31 0.47
4way cassette S
(AM***FN4DEH*)
(AM***NN4DEH*)
0.45 0.45 0.45 0.45 0.57 0.69 0.69
360 cassette
(AM***KN4DEH*)
0.45 0.45 0.45 0.45 0.69 0.69 0.69
Floor Standing Unit
(AM***FNFDEH*)
0.22 0.32 0.32
ERV plus
(AM***FNKDEH*)
0.11 0.36
4way cassette
S (600x600)
(AM***FNNDEH*)
(AM***NNNDEH*)
0.29 0.29 0.29 0.29 0.37 0.37 0.37
Slim duct
(AM***FNLDEH*)
0.17 0.17 0.17 0.26 0.35 0.35 0.45 0.42 0.42 0.62 0.62
Home duct
(AM***MNLDEH*)
(AM***KNLDEH*)
0.13 0.13 0.13 0.17 0.24 0.24 0.31
MSP duct(MA duct)
(AM****NMDEH*)
0.24 0.24 0.24 0.28 0.28 0.28 0.32 0.54 0.68 0.68 0.91
MSP duct(Duct S)
(AM***ANMPKH*)
0.45 0.45 0.45 0.45 0.8 0.84 0.84 0.84
Ceiling
(AM***FNCDEH*/
AM***JNCDKH*)
0.39 0.39 0.56 0.95
Console
(AM****NJDEH*)
0.16 0.27 0.27 0.27 0.27
Neo forte
(AM***FNTDEH*)
0.24 0.24 0.24 0.24 0.36 0.36
Neo forte (with EEV)
(AM***FNQDEH*)
0.34 0.34 0.34 0.34 0.51 0.51 0.51
Boracay
(AM***KNTD*H*)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
Boracay (with EEV)
(AM***KNQD*H*)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
AR5000
(AM***JNAD*H*)
0.16 0.16 0.19 0.25 0.25 0.52 0.52 0.52
AR5000 (with EEV)
(AM***JNVD*H*)
0.22 0.22 0.25 0.34 0.34 0.71 0.71 0.71
MAX4 (with EEV)
(AM***MNQD*H*)
0.68
QMD RAC (with EEV)
(AM***TNVDKH*)
(AM***TNQDKH*)
0.23 0.23 0.32 0.32 0.48 0.48 0.48 0.64
HSP duct
(AM***FNHDEH*)
0.68 0.68 0.68 1 .18 1 .18
HSP duct (Duct S)
(AM***ANHPKH*)
0.84 0.84 0.84
Big duct
(AM***JNH*KH*)
1 .15 1 .15
OAP duct
(AM****NEP*H*)
0.68 1.18 1.18
PAC (AM***JNPDKH*) 0.69 1 .85
Hydro Unit HE
(AM****NBDEH*)
0.60 0.70 1.20
Hydro Unit HT
(AM***TNBF*B*)
0.60 note
1)
PAC (AM***JNPDKH*) 0.69 1 .85
If there is no additional refrigerant value for the indoor unit in the above table, refer to the indoor unit installation manual.

Bekijk gratis de handleiding van Samsung AM200AXVFNH, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSamsung
ModelAM200AXVFNH
CategorieAirco
TaalNederlands
Grootte9280 MB