Installation Procedure
H/P
33.6kW 40.0kW
(D)
(E)
(F)
(C)
(A)
(B)
(3)
(2)
(1)
61.6kW
Ex.) 135.2kW
Capacity (kW) No.
Pipe size (mm)
Liquid Gas
33.6 (1) Ø 12.70 Ø 28.58
73.6 (2) Ø 19.05 Ø 34.92
135.2 (3) Ø 19.05 Ø 41.28
Size of the pipe connected to the outdoor unit (A) Size of the pipe between the branch joint and the indoor unit (F)
Select the size of the main pipe according to the below table.
Outdoor unit
capacity (kW)
(Cooling)
*Maximum pipe length within 90m
*Maximum pipe length over 90m
Liquid (mm) Gas (mm) Liquid (mm) Gas (mm)
Capacity 25
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
25 < Capacity32 Ø 22.22 Ø 25.40
note1)
32 < Capacity39
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
39 < Capacity ≤ 44
44 < Capacity48
Ø 31.75
note2)
48 < Capacity55
Ø 15.88 Ø 19.05
55 < Capacity66
66 < Capacity72
Ø 34.92 Ø 38.10
note3)
72 < Capacity100
Ø 19.05 Ø 22.22100 < Capacity139
Ø 41.28
Ø 41.28
139 < Capacity173
Ø 53.98173 < Capacity252 Ø 22.22
Ø 53.98
Ø 25.40
note1)
252 < Capacity Ø 25.40 Ø 28.58
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor
unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
For the case that the diameter of the default pipe of an outdoor unit does not match that of
the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Make a selection according to indoor unit capacity.
Indoor unit capacity
(kW)
Pipe size (O.D. mm)
Liquid Gas
6.0 and below Ø 6.35 Ø 12.70
6.1 ~ 16.0 Ø 9.52 Ø 15.88
16.1 ~ 23.0 Ø 9.52 Ø 19.05
Over 23.0 Ø 9.52 Ø 22.22
Branch joint (C~E)
Branch joint between outdoor units (C)
Classification Model name Specification (kW)
Y-joint for outdoor
unit (C)
MXJ-TA3819M 135.2 and below
MXJ-TA4422M Over 135.2
First branch joint (D)
Make a selection according to outdoor unit capacity.
Classification Model name of the branch joint Outdoor unit capacity (kW)
Y-joint (D)
MXJ-YA1509M 15.0 and below
MXJ-YA2512M 15.1 ~ 40.0
MXJ-YA2812M 40.1 ~ 45.0
MXJ-YA2815M 45.1 ~ 70.3
MXJ-YA3419M 70.4 ~ 98.4
MXJ-YA4119M 98.5 ~ 135.2
MXJ-YA4422M Over 135.2
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected
after the branch.
However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe
connected to the outdoor unit (D), apply the pipe size (D).
1) Y-joint
Classification Model name Specification (kW)
Y-joint (E)
MXJ-YA1509M 15.0 and below
MXJ-YA2512M 15.1 ~ 40.0
MXJ-YA2812M 40.1 ~ 45.0
MXJ-YA2815M 45.1 ~ 70.3
MXJ-YA3419M 70.4 ~ 98.4
MXJ-YA4119M 98.5 ~ 135.2
MXJ-YA4422M Over 135.2
2) Distribution header
Classification Model name Specification (kW)
Distribution header (E)
MXJ-HA2512M 45.0 and below (for 4 rooms)
MXJ-HA3115M 70.3 and below (for 8 rooms)
MXJ-HA3819M 70.4 ~ 135.2
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after
the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe
connected to the outdoor unit (A), apply the pipe size (A).
Indoor unit
capacity (kW)
Branch pipe length within 45m
Branch pipe length between
45~90m
Liquid (mm) Gas (mm) Liquid (mm) Gas (mm)
Capacity 15
Ø 9.52
Ø 15.88
Ø 12.70
Ø 19.05
15 < Capacity ≤ 25
Ø 19.05 Ø 22.22
25 < Capacity ≤ 32 Ø 22.22 Ø 25.40
note1)
32 < Capacity ≤ 39
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
39 < Capacity ≤ 44
44 < Capacity ≤ 48
Ø 31.75
note2)
48 < Capacity ≤ 55
Ø 15.88 Ø 19.0555 < Capacity ≤ 66
66 < Capacity ≤ 72
Ø 34.92 Ø 38.10
note3)
72 < Capacity100
Ø 19.05 Ø 22.22100 < Capacity 139
Ø 41.28
Ø 41.28
139 < Capacity173
Ø 53.98173 < Capacity ≤ 252 Ø 22.22
Ø 53.98
Ø 25.40
note1)
252 < Capacity Ø 25.40 Ø 28.58
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.