Refrigerant pipe installation
English
Installation Procedure
Allowable length of the refrigerant pipe and the installation examples
Classification Single Installation Module installation
Installing only with Y-joint
Branch joint
Outdoor unit
Indoor unit
b
h i j k l m n
H2
1 2 3 4 5 6 7
8
a
A B C D E F G
H1
c d e f g p
Branch joint
Outdoor unit
Indoor unit
b
h i j k l m n
H2
1 2 3 4 5 6 7
8
a
A
B C D E F G
H1
c d e f g p
Installing with Y-joint and
distribution header
b
j
H2
1 2 3 4 5 6
7 8
a
A B
i
k
H1
c d e f
g
h
Branch joint
Distribution header
Outdoor unit
Indoor unit
Indoor unit
1 2 3 4 5 6
7 8
B
H1
a
b
j
H2
k
i
A
dc e f
g
h
Outdoor unit
Distribution header
Branch joint
Installing only with distribution
header
i
8
7654321
cb
a
fed h
H1
H2
g
Outdoor unit
Indoor unit
Distribution header
e f
g
h
i
H2
H1
8
7654321
dcb
a
Outdoor unit
Indoor unit
Distribution header
Classification Example Remarks
Maximum
allowable
length of pipe
Outdoor
unit ~
Indoor unit
Actual length
(Equivalent
length)
200 m(656')
and below
[220 m(722')
and below]
Installing only with
Y-joint
a+b+c+d+e+f+g+p ≤
200 m(220 m)/656'(722')
Equivalent length
Y-joint: 0.5 m (1.64'),
Distribution header:
1 m(3.28')
Installing with Y-joint
and distribution header
a+b+h ≤ 200m (220m), a+i+k ≤
200 m(220 m)/656'(722')
Installing only with
distribution header
a+i ≤ 200 m(220 m)/656'(722')
Total length
of pipe (m)
1000 m(3281')
or less
Installing only with
Y-joint
a+b+c+d+e+f+g+h+i+
j+k+l+m+n+p ≤ 1000 m (3281')
-
Installing with Y-joint
and distribution header
a+b+c+d+e+f+g+h+i+j+k
≤ 1000 m (3281')
-
Installing only with
distribution header
a+b+c+d+e+f+g+h+i
≤ 1000 m (3281')
-
Outdoor
unit ~
Outdoor unit
(Module
installation)
Pipe length
10 m (33') or
less
x ≤ 10 m (33'), y ≤ 10 m (33'), z ≤ 10 m (33')
x
z
y
Equivalent
length
13 m (43') or
less
x ≤ 13 m (43'), y ≤ 13 m (43'), z ≤ 13 m (43')
Maximum
allowable
height
difference of
pipe
Outdoor unit
~ Indoor unit
110/110 m(361'/361')
Note 2)
H1 ≤ 110/110 m(361'/361')
Indoor unit
~ Indoor unit
50 m (164') or less H2 ≤ 50 m (164')
But, when wall-mount type indoor units with EEV (AM****NQD* / AM****NVD*) is installed, H2 is 15 m(49') or less.
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 28DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 28 2022-09-13 오전 9:34:132022-09-13 오전 9:34:13