Samsung AM180CXVAJH handleiding

58 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 20 van 58
20
Refrigerant pipe installation
English
Installation Procedure
Additional refrigerant
1/2” (5m/16.4’)
1/2” (5m/16.4’)
1/2” (5m/16.4’)
1/4” (5m/16.4’)
1/4” (10m/32.8’)
1/4” (15m/49.2’)
3/8”
(10m/32.8’)
3/8”
(10m/32.8’)
3/8” (10m/32.8’)
3/8”
(10m/32.8’)
1/4” (5m/16.4’)
3/8” (10m/32.8’)
144MBH (12Ton)
12MBH
24MBH
24MBH
18MBH
18MBH
18MBH
18MBH
12MBH
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit [lb(kg)]
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification AM080CXVAFH AM100CXVAFH AM120CXVAFH AM140CXVAFH AM160CXVAFH AM180CXVAFH AM200CXVAFH AM220CXVAFH
Basic amount [lb(kg)] 15.4 (7.0) 15.4 (7.0) 15.4 (7.0) 17.6 (8.0) 17.6 (8.0) 23.1 (10.5) 23.1 (10.5) 23.1 (10.5)
Classification AM240CXVAFH AM260CXVAFH AM080CXVAFC AM100CXVAFC AM120CXVAFC AM140CXVAFC AM160CXVAFC AM180CXVAFC
Basic amount [lb(kg)] 30.9 (14.0) 30.9 (14.0) 15.4 (7.0) 15.4 (7.0) 15.4 (7.0) 17.6 (8.0) 17.6 (8.0) 23.1 (10.5)
Classification AM200CXVAFC AM220CXVAFC AM240CXVAFC AM260CXVAFC AM080CXVAJH AM100CXVAJH AM120CXVAJH AM140CXVAJH
Basic amount [lb(kg)] 23.1 (10.5) 23.1 (10.5) 24.3 (11.0) 24.3 (11.0) 15.4 (7.0) 15.4 (7.0) 15.4 (7.0) 17.6 (8.0)
Classification AM160CXVAJH AM180CXVAJH AM200CXVAJH AM220CXVAJH AM240CXVAJH AM260CXVAJH AM280CXVAJH AM300CXVAJH
Basic amount [lb(kg)] 17.6 (8.0) 23.1 (10.5) 23.1 (10.5) 23.1 (10.5) 30.9 (14.0) 30.9 (14.0) 30.9 (14.0) 34.2 (15.5)
Classification AM320CXVAJH AM340CXVAJH AM080CXVAJC AM100CXVAJC AM120CXVAJC AM140CXVAJC AM160CXVAJC AM180CXVAJC
Basic amount [lb(kg)] 34.2 (15.5) 34.2 (15.5) 13.7 (6.2) 15.4 (7.0) 15.4 (7.0) 17.6 (8.0) 17.6 (8.0) 23.1 (10.5)
Classification AM200CXVAJC AM220CXVAJC AM240CXVAJC AM260CXVAJC AM280CXVAJC AM300CXVAJC AM320CXVAJC AM340CXVAJC
Basic amount [lb(kg)] 23.1 (10.5) 23.1 (10.5) 24.3 (11.0) 24.3 (11.0) 24.3 (11.0) 24.3 (11.0) 27.6 (12.5) 27.6 (12.5)
Amount of additional refrigerant depending on the pipe size ( )
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe
[mm (inch)]
Φ1/4
(Φ6.35)
Φ3/8
(Φ9.52)
Φ1/2
(Φ12.7)
Φ5/8
(Φ15.88)
Φ3/4
(Φ19.05)
Φ7/8
(Φ22.22)
Φ1
(Φ25.4)
Φ1 1/8
(Φ28.58)
Additional amount
[lb/ft (kg/m)]
0.013
(0.02)
0.04
(0.06)
0.084
(0.125)
0.121
(0.18)
0.181
(0.27)
0.235
(0.35)
0.356
(0.53)
0.437
(0.65)
Amount of refrigerant
added when the diameter
of liquid pipe is reduced
[kg/m (lb/ft)]
-
0.054
(0.08)
0.087
(0.13)
0.131
(0.195)
0.188
(0.28)
0.282
(0.42)
0.356
(0.53)
-
For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.0067lb/ft (0.01kg/m) regardless of the pipe size.