Refrigerant pipe installation
English
Installation Procedure
16Ton 12Ton
(D)
(E)
(C)
(A)
(B)
(3)
(2)
(1)
6Ton
Ex.) 34 Ton
Ton No.
Pipe size (O.D)
Liquid pipe Gas pipe
mm inch mm inch
16 (1) 15.88 5/8 28.58 11/8
28 (2) 19.05 3/4 34.92 13/8
34 (3) 19.05 3/4 41.28 15/8
Size of the pipe connected to the outdoor unit (A) Branch joint (C~E)
Select the size of the main pipe according to the below table.
Outdoor unit
capacity (MBH)
(Cooling)
Outdoor unit
capacity (kW)
(Cooling)
*Maximum pipe length within
295ft (90m)
*Maximum pipe length over
295ft (90m)
Liquid Gas Liquid Gas
inch mm inch mm inch mm inch mm
Capacity 85 Capacity 25
Ø3/8 Ø9.52
Ø3/4 Ø19.05
Ø1/2 Ø12.70
Ø7/8 Ø22.22
85 < Capacity99 25 < Capacity29
Ø7/8 Ø22.22 Ø1
note1)
Ø25.40
note1)
99 < Capacity 120 29 < Capacity ≤ 35
Ø1/2 Ø12.70
Ø1 1/8 Ø28.58
Ø5/8 Ø15.88
Ø1 1/8 Ø28.58
120 < Capacity 140 35 < Capacity ≤ 41
140 < Capacity160 41 < Capacity47
Ø1 1/4
note2)
Ø31.75
note2)
160 < Capacity 181 47 < Capacity ≤ 53
Ø5/8 Ø15.88 Ø3/4 Ø19.05
181 < Capacity ≤ 222 53 < Capacity ≤ 65
222 < Capacity ≤ 240 65 < Capacity70
Ø1 3/8 Ø34.92
Ø1 3/8 Ø34.92
240 < Capacity ≤ 336
70 < Capacity98
Ø3/4 Ø19.05 Ø7/8 Ø22.22
Ø1 1/2
note3)
Ø38.10
note3)
336 < Capacity467 98 < Capacity 137
Ø1 5/8 Ø41.28 Ø1 5/8 Ø41.28
467 < Capacity ≤ 583 137 < Capacity 171
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø1” (25.40mm) pipe is not available on site, use Ø1 1/8” (28.58mm) pipe.
Note2) If Ø1 1/4” (31.75mm) pipe is not available on site, use Ø1 3/8” (34.92mm) pipe.
Note3) If Ø1 1/2” (38.10mm) pipe is not available on site, use Ø1 5/8” (41.28mm) pipe.
For the case that the diameter of the default pipe of an outdoor unit does not match that of
the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Branch joint between outdoor units (C)
Select a branch joint according to the sum of the capacity of outdoor units connected to the
branch joint.
Classification
Outdoor unit capacity
Model name
MBH kW
Y-joint for outdoor
unit (C)
Capacity ≤ 467 Capacity 137 MXJ-TA3819M
467 < Capacity 137 < Capacity MXJ-TA4422M
First branch joint (D)
Select according to the sum of the capacity of the outdoor unit.
Classification
Outdoor unit capacity
Model name
MBH kW
Y-joint (D)
Capacity 140 Capacity ≤ 41 MXJ-YA2512M
Capacity 160 Capacity ≤ 47 MXJ-YA2812M
Capacity ≤ 239 Capacity ≤ 70 MXJ-YA2815M
Capacity ≤ 336 Capacity ≤ 98 MXJ-YA3419M
Capacity ≤ 467 Capacity 137 MXJ-YA4119M
467 < Capacity 137 < Capacity MXJ-YA4422M
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected
after the branch.
However, if the branch joints (E) is bigger than the first branch joint (D), apply the branch
joint of the same size as the first branch joint (D).
Classification
Indoor unit capacity
Model name
MBH kW
Y-joint (E)
Capacity < 55 Capacity < 16 MXJ-YA1509M
55 ≤ Capacity < 133 16 ≤ Capacity < 39 MXJ-YA2512M
133 ≤ Capacity < 172 39 ≤ Capacity < 50.4 MXJ-YA2812M
172 ≤ Capacity < 248 50.4 ≤ Capacity < 72.8 MXJ-YA2815M
248 ≤ Capacity < 344 72.8 ≤ Capacity < 100.8 MXJ-YA3419M
344 ≤ Capacity < 478 100.8 ≤ Capacity < 140 MXJ-YA4119M
478 < Capacity 140 < Capacity MXJ-YA4422M
Distribution
header (E)
Capacity < 172 (for 4 rooms) Capacity < 50.4 (for 4 rooms) MXJ-HA2512M
Capacity < 248 (for 8 rooms) Capacity < 72.8 (for 8 rooms) MXJ-HA3115M
Capacity < 478 (for 8 rooms) Capacity < 140 (for 8 rooms) MXJ-HA3819M
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after
the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe
connected to the outdoor unit (A), apply the pipe size (A).
Indoor unit
capacity (MBH)
Indoor unit
capacity (kW)
Branch pipe length within
148ft (45m)
Branch pipe length between
148ft~295ft (45~90m)
Liquid Gas Liquid Gas
inch mm inch mm inch mm inch mm
Capacity < 19 Capacity < 5.7
Ø1/4 Ø6.35 Ø1/2 Ø12.70 Ø3/8 Ø9.52 Ø5/8 Ø15.88
19 ≤ Capacity < 55 5.7 ≤ Capacity < 16
Ø3/8 Ø9.52
Ø5/8 Ø15.88
Ø1/2 Ø12.70
Ø3/4 Ø19.05
55 ≤ Capacity < 79 16 ≤ Capacity < 23.2
Ø3/4 Ø19.05 Ø7/8 Ø22.22
79 ≤ Capacity < 115 23.2 ≤ Capacity < 33.6
Ø7/8 Ø22.22 Ø1
note1)
Ø25.40
note1)
115 ≤ Capacity < 133 33.6 ≤ Capacity < 39
Ø1/2 Ø12.70
Ø1 1/8 Ø28.58
Ø5/8 Ø15.88
Ø1 1/8 Ø28.58
133 ≤ Capacity < 150 39 ≤ Capacity < 44
150 ≤ Capacity < 172 44 ≤ Capacity < 50.4
Ø1 1/4
note2)
Ø31.75
note2)
172 ≤ Capacity < 229 50.4 ≤ Capacity < 67.2
Ø5/8 Ø15.88 Ø3/4 Ø19.05
230 ≤ Capacity < 248 67.2 ≤ Capacity < 72.8
Ø1 3/8 Ø34.92
Ø1 3/8 Ø34.92
248 ≤ Capacity < 344
72.8 ≤ Capacity
< 100.8
Ø3/4 Ø19.05 Ø7/8 Ø22.22
Ø1 1/2
note3)
Ø38.10
note3)
344 ≤ Capacity < 392 100.8 ≤ Capacity < 115
Ø1 5/8 Ø41.28
Ø1 5/8 Ø41.28
392 ≤ Capacity < 592 115 ≤ Capacity < 173.6
Ø1 3/4
note4)
Ø44.45
note4)
592 ≤ Capacity < 676 173.6 ≤ Capacity < 198
Ø7/8 Ø22.22
Ø1 3/4
note4)
Ø44.45
note4)
Ø1
note1)
Ø25.40
note1)
Ø2 1/8 Ø53.98
676 ≤ Capacity < 860 198 ≤ Capacity < 252
Ø2 1/8 Ø53.98
860 ≤ Capacity 252 ≤ Capacity
Ø1
note1)
Ø25.40
note1)
Ø1 1/8 Ø28.58
Note1) If Ø1” (25.40mm) pipe is not available on site, use Ø1 1/8” (28.58mm) pipe.
Note2) If Ø1 1/4” (31.75mm) pipe is not available on site, use Ø1 3/8” (34.92mm) pipe.
Note3) If Ø1 1/2” (38.10mm) pipe is not available on site, use Ø1 5/8” (41.28mm) pipe.
Note4) If Ø1 3/4” (44.45mm) pipe is not available on site, use Ø2 1/8” (53.98mm) pipe.
Size of the pipe between the branch joint and the indoor unit (F)
Select according to the capacity of the indoor unit.
Indoor unit capacity Liquid Gas
MBH kW inch mm inch mm
Capacity ≤ 20 Capacity ≤ 6 Ø1/4 Ø6.35 Ø1/2 Ø12.7
20 < Capacity ≤ 54 6 < Capacity16 Ø3/8 Ø9.52 Ø5/8 Ø15.88
54 < Capacity ≤ 78 16 < Capacity ≤ 23 Ø3/8 Ø9.52 Ø3/4 Ø19.05
78 < Capacity 23 < Capacity Ø3/8 Ø9.52 Ø7/8 Ø22.22
If the criteria for selecting the branch in the outdoor installation manual and the branch
installation manual are different, please select the branch in accordance with the outdoor
installation manual.
(F)
DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 18DB68-11976A-00_IM_DVM S2 Outdoor_SA_EN_.indd 18 2022-09-13 오전 9:34:072022-09-13 오전 9:34:07