Installation Procedure
Additional refrigerant
H/P H/R
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø6.35 (5 m)
Ø6.35 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52
(10 m)
Ø6.35 (5 m)
Ø9.52 (10 m)
45.0kW
4.5kW
5.6kW
5.6kW
7.1kW
7.1kW
7.1kW
7.1kW
3.6kW
Ø9.52 (1m)
Ø15.88 (5 m)
Ø19.05 (10 m)
Ø12.70 (10 m)
Ø9.52
(15 m)
Ø9.52 (10 m)
Ø12.70 (10 m)
Ø9.52 (18 m)
Ø9.52
(18 m)
Ø9.52 (25 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
MCU
MCU
Ø6.35(2 m)
2.8kW
11.2kW
11.2kW
7.1kW
11.2kW
11.2kW
11.2kW
11.2kW
Ø6.35(15 m)
78.4 kW (50.4 kW + 28.0 kW)
Refrigerant pipe installation
• Basic amount of refrigerant within the outdoor unit (kg)
– Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classification AM080DXVGGH/SA AM100DXVGGH/SA AM120DXVGGH/SA AM140DXVGGH/SA AM160DXVGGH/SA AM180DXVGGH/SA
Basic amount 7.0 7.0 7.0 8.0 10.5 10.5
Classification AM200DXVGGH/SA AM220DXVGGH/SA AM240DXVGGH/SA AM260DXVGGH/SA
Basic amount 10.5 10.5 14 14
Classification AM080DXVGGR/SA AM100DXVGGR/SA AM120DXVGGR/SA AM140DXVGGR/SA AM160DXVGGR/SA AM180DXVGGR/SA
Basic amount 7.0 7.0 7.0 8.0 10.5 10.5
Classification AM200DXVGGR/SA AM220DXVGGR/SA AM240DXVGGR/SA AM260DXVGGR/SA
Basic amount 10.5 10.5 14.0 14.0
• Amount of additional refrigerant depending on the pipe size ( )
– Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount
(kg/m)
0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
Amount of
refrigerant added
when the diameter
of liquid pipe is
reduced (kg/m)
- 0.08 0.13 0.195 0.28 0.42 0.53 -
– For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of the pipe size.