15
English
Installation Procedure
H/P
28.0kW 50.4kW
(D)
(E)
(C)
(A)
(B)
(3)
(2)
(1)
72.8kW
Ex.) 151.2kW
Capacity (kW) No.
Pipe size (mm)
Liquid Gas
28.0 (1) Ø 9.52 Ø 22.22
78.4 (2) Ø 19.05 Ø 34.92
151.2 (3) Ø 19.05 Ø 41.28
Size of the pipe connected to the outdoor unit (A) Branch joint (C~E)
Select the size of the main pipe according to the below table.
Outdoor unit
capacity (kW)
(Cooling)
*Maximum pipe length within 90m
*Maximum pipe length over 90m
Liquid (mm) Gas (mm) Liquid (mm) Gas (mm)
Capacity ≤ 25
Ø 9.52
Ø 19.05
Ø 12.70
Ø 22.22
25 < Capacity29 Ø 22.22 Ø 25.40
note1)
29 < Capacity35
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
35 < Capacity41
41 < Capacity47
Ø 31.75
note2)
47 < Capacity53
Ø 15.88 Ø 19.05
53 < Capacity65
65 < Capacity70
Ø 34.92
Ø34.92
70 < Capacity98
Ø 19.05 Ø 22.22
Ø 38.10
note3)
98 < Capacity137
Ø 41.28
Ø 41.28
137 < Capacity171 Ø44.45
note4)
171 < Capacity 193
Ø 22.22
Ø44.45
note4)
Ø 25.40
note1)
Ø 53.98193 < Capacity255
Ø 53.98
255 < Capacity Ø 25.40
note1)
Ø 28.58
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
Note4) If Ø 44.45 pipe is not available on site, use Ø 53.98 pipe.
For the case that the diameter of the default pipe of an outdoor unit does not match that of
the pipe installed on the site, a socket is provided by default together with the outdoor unit.
Branch joint between outdoor units (C)
Select a branch joint according to the sum of the capacity of outdoor units connected to the
branch joint.
Classification Outdoor unit capacity (kW) Model name
Y-joint for outdoor
unit (C)
Capacity 137 MXJ-TA3419M
137 < Capacity MXJ-TA4122M
First branch joint (D)
Select according to the sum of the capacity of the outdoor unit.
Classification Outdoor unit capacity (kW) Model name
Y-joint (D)
Capacity ≤ 41 MXJ-YA2512M
Capacity ≤ 47 MXJ-YA2812M
Capacity ≤ 70 MXJ-YA2815M
Capacity ≤ 98 MXJ-YA3419M
Capacity 137 MXJ-YA4119M
137 < Capacity MXJ-YA4422M
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected
after the branch.
However, if the branch joints (E) is bigger than the first branch joint (D), apply the branch
joint of the same size as the first branch joint (D).
Classification
Indoor unit capacity (kW)
Model name
Y-joint (E)
Capacity < 16 MXJ-YA1509M
16 ≤ Capacity < 39 MXJ-YA2512M
39 ≤ Capacity < 50.4 MXJ-YA2812M
50.4 ≤ Capacity < 72.8 MXJ-YA2815M
72.8 ≤ Capacity < 100.8 MXJ-YA3419M
100.8 ≤ Capacity < 140 MXJ-YA4119M
140 < Capacity MXJ-YA4422M
Distribution header (E)
Capacity < 50.4 (for 4 rooms) MXJ-HA2512M
Capacity < 72.8 (for 8 rooms) MXJ-HA3115M
Capacity < 140 (for 8 rooms) MXJ-HA3819M
If the criteria for selecting the branch in the outdoor installation manual and the branch
installation manual are different, please select the branch in accordance with the outdoor
installation manual.
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe
connected to the outdoor unit (A), apply the pipe size (A).
Indoor unit
capacity (kW)
Branch pipe length within 45m
Branch pipe length between
45~90m
Liquid (mm) Gas (mm) Liquid (mm) Gas (mm)
Capacity < 5.7 Ø6.35 Ø 12.70 Ø 9.52 Ø 15.88
5.7 ≤ Capacity < 16
Ø 9.52
Ø 15.88
Ø 12.70
Ø 19.05
16 ≤ Capacity < 23.2 Ø 19.05 Ø 22.22
23.2 ≤ Capacity < 33.6
Ø 22.22 Ø 25.40
note1)
33.6 ≤ Capacity < 39
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
39 ≤ Capacity < 44
44 ≤ Capacity < 50.4
Ø 31.75
note2)
50.4 ≤ Capacity < 67.2
Ø 15.88 Ø 19.05
67.2 ≤ Capacity < 72.8
Ø 34.92
Ø34.92
72.8 ≤ Capacity < 100.8
Ø 19.05 Ø 22.22
Ø 38.10
note3)
100.8 ≤ Capacity < 115
Ø 41.28
Ø 41.28
115 ≤ Capacity < 173.6
Ø44.45
note4)
173.6 ≤ Capacity < 198
Ø 22.22
Ø44.45
note4)
Ø 25.40
note1)
Ø 53.98198 ≤ Capacity < 252
Ø 53.98
252 ≤ Capacity Ø 25.40
note1)
Ø 28.58
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe.
Note4) If Ø 44.45 pipe is not available on site, use Ø 53.98 pipe.
Size of the pipe between the branch joint and the indoor unit (F)
Select according to the capacity of the indoor unit.
Indoor unit capacity
(kW)
Liquid (mm) Gas (mm)
Capacity ≤ 6 Ø 6.35 Ø 12.70
6 < Capacity16 Ø 9.52 Ø 15.88
16 < Capacity ≤ 23 Ø 9.52 Ø 19.05
23 < Capacity Ø 9.52 Ø 22.22
(F)