Installation Procedure
56
English
Installation Procedure
(*1) Height difference : The difference of the height between the corresponding indoor unit and the indoor
unit installed at the lowest place. For example, When the indoor unit is installed 40m higher than the
indoor unit installed at the lowest place, select the option “1”.
(*2) The difference between the pipe length of the indoor unit installed at farthest place from an outdoor unit
and the pipe length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100 m(328 ft.) and the corresponding indoor unit is 40 m
aw
ay from an outdoor unit, select the option “2”. (100 - 40 = 60m)
(*3) For MTFC option, MTFC(Multi Tenant Function Controller) kit is required.
(*4) Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when
SEG15 is set to using external heater.
Example 1) Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: The hot water heater is turned on
at the s
ame time as the heating thermostat is on, and turned off when the heating thermostat is off.
Example 2) Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”: Room temp. ≤ set temp. + f
(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 4.5 °C for 10 minutes. Room temp. >
set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 4.5 °C + 1 °C (1 °C is the Hysteresis for
On/Off selection.)
Additional information on SEG3, 4, 5, 6, 8, 9
When SEG3 is set to 1 and the HR-specific auto changeover function is run, the indoor unit operates as shown
in the following figure:
Cooling thermo off
Cooling thermo on
Heating thermo off
Heating thermo on
Reference temperature for change from
heating to cooling
Set temperature
for Auto mode
Ref
erence
temperature
for cooling
Tempe
rature
Ts
Reference temperature for
cooling
Ref
erence temperature for heating
A: Set with SEG4 (˚C)
B: Set with SEG5 (˚C)
C: Set with SEG6 (˚C)
D: Set with SEG8 (˚C)
b
d
a
c
B
A
C
D
The mode change between the Cool and Heat modes is made only when the thermo off state is maintained for
the period of time set with SEG9.
DB68-13032A-00_IBIM_DVM R32 WindFree 1,4way_EU_EN_.indd 56DB68-13032A-00_IBIM_DVM R32 WindFree 1,4way_EU_EN_.indd 56 2024-07-29 오전 10:10:542024-07-29 오전 10:10:54