Refrigerant pipe installation
English
Installation Procedure
Amount of additional refrigerant for each indoor unit ( )
(Unit: kg)
Model
Refrigerant Amount (kg /Unit)
1.5 1.7 2.2 2.8 3.2 3.6 4.0 4.5 5.6 6.0 7.1 8.2 9.0 9.3 11.0 11.2 12.8 14.0 16.0 18.0 22.0 22.4 25.0 28.0 32.0 50.0 500CMH 1000CMH
Interior 1way cassette (JSF-0)
(AM***HN1DEH/**)
(AM***NN1PEH/**)
0.15 0.15
Slim 1way cassette (JSF-1/JSF-2)
(AM***F(J/N)N1DEH/**)
0.25 0.25 0.25 0.32 0.32
2way cassette
(AM****N2DEH/**)
0.31 0.47
4way cassette S(600x600)
(AM****NNDEH/**)
0.29 0.29 0.29 0.29 0.37 0.37 0.37
4way cassette S
(AM***F(N)N4DEH/**)
0.45 0.45 0.45 0.45 0.57 0.69 0.69
4way cassette S
(AM****N4FEH/**)
0.69 0.69 0.69 1.00 1.00 1.00 1.00 1.00 1.00
360 cassette
(AM***KN4DEH/**)
0.45 0.45 0.45 0.45 0.69 0.69 0.69
Duct S (AM****NMPKH/**) 0.22 0.22 0.22 0.22 0.31 0.38 0.38 0.38
Duct S (AM****NMPKH9**) 0.31 0.31 0.38 0.38 0.38
Duct S (AM***HNHPKH/**) 0.38 0.38 0.38
Home Duct (AM***KNLDEH/**)
0.13 0.13 0.13 0.17
Home Duct (AM***MNLDEH/**)
0.24 0.24 0.31
Slim duct (AM***FNLDEH/**) 0.17 0.17 0.17 0.26 0.35 0.35 0.45 0.42 0.42 0.62 0.62
Slim duct(with drain pump)
(AM***KNLDEH/**)
0.35 0.35 0.45 0.42 0.42 0.62 0.62
Slim duct (AM***FNLF(P)EH/**)
0.62 0.45 0.45 0.62 0.62 0.62
Slim duct (AM***NNLFEH/**) 0.62 0.62
MSP duct (AM****NMDEH***)
0.24 0.24 0.24 0.28 0.28 0.28 0.32 0.54 0.68 0.68 0.91
HSP duct (AM****NHDEH/**) 0.68 0.68 0.68 1.18 1.18
HSP duct (AM****NHF(P)EH/**)
1.18 1.18 1.18 1.18 1.18 1.18 1.18
Big duct (AM***JNHF(P)KH/**)
1.15 1.15
OAP duct (AM****NEPEH/**) 0.68 1.18 1.18
Concealed Floor Standing
(AM****NFDEH/**)
0.22 0.32 0.32
Floor Standing
(AM****NPDKH/**)
0.69 1.85
Ceiling (AM****NCDEH/**)
(AM****NCDKH/**)
0.39 0.39 0.56 0.95
Console (AM****NJDEH/**) 0.16 0.27 0.27 0.27 0.27
Wall mounted (Neo forte)
(AM***F(H)NTDEH/**)
0.24 0.24 0.24 0.24 0.36 0.36
Wall mounted(Neo forte with EEV)
(AM***F(H)NQDEH/**)
0.34 0.34 0.34 0.34 0.51 0.51 0.51
Wall mounted(AR5000)
(AM****NADKH/**)
0.16 0.16 0.19 0.25 0.25 0.52 0.52 0.52
Wall mounted(AR5000 with EEV)
(AM****NVDE(K)H/**)
0.22 0.22 0.25 0.34 0.34 0.71 0.71 0.71
Wall mounted(Boracay)
(AM***KNTDEH/**)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
Wall mounted(Boracay with EEV)
(AM***KNQDEH/**)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
Wall mounted(MAX4 with EEV)
(AM***MNQDEH/**)
0.68
ERV plus (AM****NKDEH/**) 0.11 0.36
Hydro Unit HE (AM****NBDEH/**)
0.60 0.70 1.20
Hydro Unit HT (AM****NBF*B/**)
0.60 note
1)
MCU (MCU-S*NE**N) 0.50
4Way CST (AM***AN4PKH/**)
0.45 0.45 0.45 0.60 0.60 0.73 0.73 0.88 0.88
LSP Duct (AM***ANLDKH/**) 0.13 0.13 0.13 0.17 0.24 0.24 0.31
MSP Duct (Duct S)
(AM***ANMPKH/**)
0.45 0.45 0.45 0.45 0.45 0.45 0.80 0.84 0.84 0.84
HSP Duct (Duct S)
(AM***ANHPKH/**)
0.80 0.80 0.84 0.84 0.84 0.84
A3050 (AM***JNADKH/**) 0.16 0.16 0.19 0.25 0.25 0.52 0.52 0.52
A3050(with EEV)
(AM***JNVDKH/**)
0.22 0.22 0.25 0.34 0.34 0.71 0.71 0.71
QMD RAC (AM***TNADKH/**)
(AM***TNVDKH/**)
(AE***TNXDEG/**)
0.23 0.23 0.32 0.32 0.48 0.48 0.48 0.64
If there is no additional refrigerant value for the indoor unit in the above table, refer to the indoor unit installation manual.