This function checks amount of refrigerant in the system through refrigerant amount detection operation
Start
End
Press the K2 tact switch 5 times
Checking the amount of refrigerant
automatically
Connect the S-Net pro
Check the result with the function of the
Refrigerant Check
Normal / Excessive / Shortage Judgment not available
Enter the operation in S-Net pro
check the result on display
after the operation
CAUTION
If the temperature is out of the guaranteed range below, exact result will not be obtained.
Indoor: 20~32 °C
Outdoor: 5~43 °C
If the operation cycle is not stable, the operation of refrigerant amount check may be forcibly finished.
Accuracy of the result may decrease if the product has not been operated for a long period of time or Heat mode has been operated
before running the function of refrigerant amount check. Therefore, use the function of refrigerant amount check after operating the
product in Cool mode for at least 30 minutes.
Product may trigger system protection operation depending on the installation environment. In this case, the result of refrigerant
amount check may not be accurate.
Actions to take for the check result
Excessive amount of refrigerant
Discharge 10% of total amount of refrigerant and restart the refrigerant amount check.
Insufficient amount of refrigerant
Add 10% of the total amount of refrigerant and restart the refrigerant amount check.
Judgment not available
Check if the function of refrigerant amount check is executed within the guaranteed temperature range. Run trial operation to
check if there are other problems on the system.
Automatic refrigerant amount detection function