Setting outdoor unit option switch and key function
English
Installation Procedure
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Speed operation Main 1 7
0 0 Disabled (Factory default)
Enabling this setting will command
the air conditioner to cool/heat faster
at initial start-up.
However, this function will not work
when High-head condition setting
or Long-piping condition setting is
enabled.
0 1 Enabled
Max. capacity
restriction
Main 1 8
0 0 Enabled (Factory default) Restrict excessive capacity increase
when operating indoor units with
small capacity
0 1 Disabled
Unused option Main 1 9 0 0 Unused option Unused option by this model
Unused option Main 2 0 0 0 Unused option Unused option by this model
LA KIT option Main 2 1
0 0 Disabled (Factory default)
Set when LA KIT is installed.
0 1 Enabled
Emergency
operation for indoor
unit communication
error
Main 2 2
0 0 Disabled (Factory default)
When set, emergency operation
is possible even if an indoor
communication error occurs.
0 1
Indoor high humidity condition
(operating for up to 12hours)
0 2
Indoor low humidity condition
(operating for up to 24hours)
Base Heater Main 2 3
0 0 Disabled (Factory default)
Set when Base Heater is installed.
0 1 Enabled
Inverter Carrier
Frequency
Main 2 4
0 0 Disabled (default)
Set inverter carrier frequency
0 1 8kHz
Aux Heater’s
interworking control
for cycle heating
(cooling priority
control)
Main 2 5
0 0 Not applied
When using the Aux Heating, set the
delay time for Switching from cooling
to heating.
※ Unused by the cooling only models
0 1 Switching delay to heating (30 mins.)
0 2 Switching delay to heating (15 mins.)
0 3 Switching delay to heating (10 mins.)
0 4 Switching delay to heating (5 mins.)
0 5 Not switching delay
Auto Change Over Main 2 6
0 0 Not applied
When Thermo off for all running indoor
units, change the operation mode.
※ Unused by the cooling only models
0 1 Applied
Emergency defrost
operation
Main 2 7
0 0 Disable (default)
You can enable this fuction, if the ice
on the outdoor Heat exchanger is not
removed even after continuous defrost
operation, emergency defrosting
operation is performed, but defrost
operation can take a long time.
0 1 Enable
Reduction of the
diameter of liquid
pipe
Main 2 8
0 0 Disable (default)
Set when piping is installed with
Reduction of the diameter of liquid
pipe.
0 1 Enable
View Mode
Unit Option
Main 2 9
0 0
Temperature : ℃
Pressure : MPa
Converts the temperature, pressure
units in the view mode(K4 switch)
0 1
Temperature : ℉
Pressure : psi
There is a risk of water leakage during emergency operation for indoor unit communication error. Please be careful when using it.