Samsung AM100AXVANR handleiding

78 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 64 van 78
64
Setting outdoor unit option switch and key function
English
Installation Procedure
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as malfunction
state.
0 1
Set compressor 1 as malfunction
state
0 2
Set compressor 2 as malfunction
state
Capacity correcton
for cooling
Main 0 1
0 0 7-9
Targeted evaporation temperature
[°C].
(When low temperature value is set,
discharged air temperature of the
indoor unit will decrease)
0 1 5-7 (Factory default)
0 2 9-11
0 3 10-12
0 4 11-13
0 5 12-14
0 6 13-15
Capacity correction
for heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
0 1 2.5
0 2 2.6
0 3 2.7
0 4 2.8
0 5 2.9
0 6 3.1
0 7 3.2
0 8 3.3
Current restriction
rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating performance
may decrease.
0 1 95 %
0 2 90 %
0 3 85 %
0 4 80 %
0 5 75 %
0 6 70 %
0 7 65 %
0 8 60 %
0 9 55 %
1 0 50 %
1 1 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
0 1
Apply setting when the product is
being installed in humid area such
as near river or lake
Fan speed correction
for outdoor unit
Individual 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's fan speed
to maximum value

Bekijk gratis de handleiding van Samsung AM100AXVANR, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSamsung
ModelAM100AXVANR
CategorieAirco
TaalNederlands
Grootte12459 MB