Installation Procedure
H/P, C/O
When all the following conditions are met, install the main liquid pipe that is one step smaller to reduce piping load and the amount of
refrigerant.
Note that the refrigerant for the main liquid pipe must be added by the specified amount upon reduction.
Condition 1: In case the length for vertical piping is less than 40 m
Condition 2: Max. length A ≥ Max. pipping length/{1 - (vertical piping length * 0,015)}
※ Max. piping length: Piping length between the outdoor unit and the farthest indoor unit (m)
• Length allowed to reduce the diameter of liquid pipe, A (equivalent length)
• When piping is installed with reduction of the diameter of liquid pipe, Please set option ‘reduction of the diameter of liquid pipe’.
Capacity
(HP)
Below 90 m Over 90m
Capacity
(HP)
Below 90 m Over 90m
Pipe
diameter
Max
length (m)
Pipe
diameter
Max
length (m)
Pipe
diameter
Max
length (m)
Pipe
diameter
Max
length (m)
8 This capacity is not supported. 54 15.88 40 19.05 130
10 This capacity is not supported.
56
15.88 40 19.05 120
12 9.52 50 12.7 200
58
15.88 40 19.05 120
14 9.52 40 12.7 190
60
15.88 40 19.05 110
16 9.52 30 12.7 150
62
19.05 90 22.22 200
18 12.7 90 15.88 200
64
19.05 90 22.22 200
20 12.7 90 15.88 200
66
19.05 90 22.22 200
22 12.7 80 15.88 200
68
19.05 90 22.22 200
24 12.7 70 15.88 200
70
19.05 80 22.22 190
26 15.88 90 19.05 200
72
19.05 80 22.22 180
28 15.88 90 19.05 200
74
19.05 70 22.22 170
30 15.88 90 19.05 200
76
19.05 70 22.22 160
32 15.88 90 19.05 200
78
19.05 70 22.22 150
34 15.88 90 19.05 200
80
19.05 60 22.22 150
36 15.88 90 19.05 200
82
19.05 60 22.22 140
38 15.88 90 19.05 200
84
19.05 60 22.22 130
40 15.88 80 19.05 200
86
19.05 50 22.22 130
42 15.88 70 19.05 200
88
19.05 50 22.22 120
44 15.88 70 19.05 200
90
19.05 50 22.22 120
46 15.88 60 19.05 180
92
This capacity is not supported.
48 15.88 60 19.05 170
94
This capacity is not supported.
50 15.88 50 19.05 150
96
This capacity is not supported.
52 15.88 50 19.05 140
98
This capacity is not supported.
e.g. In case of the site for 20HP, Max. piping length of 140 m (Horizontal piping length of 120 m & Vertical piping length of 20 m):
Max. length A ≥ Max. piping length/{1 - (Vertical piping length * 0.015)}
200 m ≥ 140 m/{1 - (20 * 0.015)} = 140 m/0.7 = 200 m
Thus, the Max. piping length of 140 m (Horizontal piping length of 120 m & Vertical piping length of 20 m) can be allowed.
Accordingly, horizontal piping of 120 m + vertical piping of 20 m (140 m in total) can be installed.