Troubleshooting
Incorrect handling of thermostat, safety valve or other valves may lead to tank rupture. When servicing the unit
follow instructions carefully:
Always turn o main power supply when water supply is being shut o.
Test the free operation of the safety valve regularly by opening the valve ensuring the water ows freely.
Electrical connection and all servicing of the electrical components should only be carried out by an authorized
electrician.
Fitting and all servicing of plumbing xtures should only be carried out by an authorized installer.
When replacing the thermostat, safety valve or any other valve or part supplied with this unit, use only approved
parts of the same specication.
WARNING
Error codes
If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT main PBA or LCD
of the wired remote controller.
Display Explanation Error Source
101 Hydro Unit / Outdoor Unit communication connection error Hydro Unit
120
Short- or open-circuit error of the room temperature sensor of the Zone 2
indoor unit (detected only when the room thermostat is used)
Hydro Unit
121
Short- or open-circuit error of the room temperature sensor of the Zone 1
indoor unit (detected only when the room thermostat is used)
Hydro Unit
122 EVA Inlet temp sensor SHORT or OPEN Hydro Unit
123 EVA Outlet temp sensor SHORT or OPEN Hydro Unit
162 EEPROM Error Hydro Unit
198 Error of Terminal Block's Thermal Fuse(Open) Hydro Unit
201 Hydro Unit / Outdoor Unit communication error(Matching error) Hydro Unit/Ourdoor Unit
202 Hydro Unit / Outdoor Unit communication error(3 min) Hydro Unit/Ourdoor Unit
203 Communication error between INVERTER and MAIN MICOM (4 min) Outdoor Unit
221 Outdoor Unit air temperature sensor error Outdoor Unit
231 Condenser temperature sensor error Outdoor Unit
251 Discharge temperature sensor error Outdoor Unit
320 OLP sensor error Outdoor Unit
403 Detection of freezing (During cooling operation) Outdoor Unit
404
Protection of Outdoor Unit when it is overload (during Safety Start, Normal
operation state)
Outdoor Unit
407 Comp down due to high pressure Outdoor Unit