Handleiding
Je bekijkt pagina 29 van 54

ENGLISH-29
02 INSTALLATION
f Because your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room
whose oor area is larger than the minimum required oor area specied in the following table:
Minimum required room area (A,m²)
m (kg) Ceiling-mounted Wall-mounted Floor-standing
≤ 1.842 No requirement
1.843 3.64 4.45 28.9
1.9 3.75 4.58 30.7
2.0 3.95 4.83 34.0
2.2 4.34 5.31 41.2
2.4 4.74 5.79 49.0
2.6 5.13 6.39 57.5
2.8 5.53 7.41 66.7
3.0 5.92 8.51 76.6
3.2 6.48 9.68 87.2
3.4 7.32 10.9 98.4
3.6 8.20 12.3 110
3.8 9.14 13.7 123
4.0 10.1 15.1 136
4.2 11.2 16.7 150
4.4 12.3 18.3 165
4.6 13.4 20.0 180
4.8 14.6 21.8 196
5.0 15.8 23.6 213
- m : Total refrigerant charge in the system
- A : Minimum required oor area
f IMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the
minimum living space of the premises.
f Minimum installation height of indoor unit is 0.6m for oor mounted, 1.8m for wall, 2.2m for ceiling.
ki]_TXYYXXhTWWptlozGyTZYGzwsp{Gv|{kvvyG䚐⣡㫴l|luUGGGY` YWYZTWXTX_GGG㝘㤸G`a\Xa[_
Bekijk gratis de handleiding van Samsung AE090CXEDGG, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Samsung |
Model | AE090CXEDGG |
Categorie | Airco |
Taal | Nederlands |
Grootte | 5125 MB |