02 INSTALLATION
f Because your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room
whose oor area is larger than the minimum required oor area specied in the following table:
Minimum required room area (A,m²)
m (kg) Ceiling-mounted Wall-mounted Floor-standing
≤ 1.842 No requirement
1.843 3.64 4.45 28.9
1.9 3.75 4.58 30.7
2.0 3.95 4.83 34.0
2.2 4.34 5.31 41.2
2.4 4.74 5.79 49.0
2.6 5.13 6.39 57.5
2.8 5.53 7.41 66.7
3.0 5.92 8.51 76.6
3.2 6.48 9.68 87.2
3.4 7.32 10.9 98.4
3.6 8.20 12.3 110
3.8 9.14 13.7 123
4.0 10.1 15.1 136
4.2 11.2 16.7 150
4.4 12.3 18.3 165
4.6 13.4 20.0 180
4.8 14.6 21.8 196
5.0 15.8 23.6 213
- m : Total refrigerant charge in the system
- A : Minimum required oor area
f IMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the
minimum living space of the premises.
f Minimum installation height of indoor unit is 0.6m for oor mounted, 1.8m for wall, 2.2m for ceiling.