Handleiding
Je bekijkt pagina 20 van 54

ENGLISH-20
Connecting the cable
Power cable specications
1 phase
Outdoor unit
Rated Voltage Range MCA MFA
Hz Volts Min Max Min. Circuit Amps. Max. Fuse Amps.
AE090CXEDEG 50 220-240 198 264 22 A 27.5 A
f The power cable is not supplied with Air to Water Heat pump.
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 57 / CENELEC:H05RN-F)
f This Equipment complies with IEC 61000-3-12.
3 Phase
Outdoor unit
Rated Voltage Range MCA MFA
Hz Volts Min Max Min. Circuit Amps. Max. Fuse Amps.
AE090CXEDGG 50 380-415 342 457 10 A 16.1 A
f The power cable is not supplied with Air to Water Heat pump.
f Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed exible cord (Code
designation IEC:60245 IEC 66 / CENELEC:H07RN-F)
f This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with distribution network operator if necessary, that the equipment is
connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].