Advanced Operation
Under the installation of both A2A (Air-To-Air type air conditioner) and A2W (Air-To-Water type hydro
unit) at the same time, our outdoor machine can supply its full capacity to the operating indoor machines
(including A2A or A2W). If there are simultaneous operating demands from many A2A machines with
A2W, the priority of controlling the outdoor machine (ex: compressor frequency) will be given to A2A,
because of their fast response for use’s comfort. Only the remaining capacity of outdoor machine will be
given to A2W during A2A’s normal operation. In this case, it might take very long time for A2W heating,
so the outdoor machine will alternate the controlling priorities between A2A and A2W with time basis.
Priority maximum operation time (at FSV #5033=0): FSV #5031 (Default “30 min.”, Range 10 ~ 90 min.),
After elapsing A2A maximum time, the outdoor machine will operate only for A2W to speed up the
A2W’s heating/cooling performance, even though there are A2A’s continuous operation demands.
Non priority minimum operation time (at FSV #5033=0): FSV #5032(Default “5 min.”, Range 3 ~ 60
min.), in this minimum time, the outdoor machine will operate only for A2W, even though there are no
more A2W’s continuous operation demands.
<Operating specifications of Time Division Switching (TDS) in accordance with FSV #5033 setting
(In case of the A2A & A2W simultaneous operation is "ON")>
FSV setting
A2A Cooling + A2W
Cooling
A2A Cooling + A2W
Heating
A2A Heating + A2W
Cooling
A2A Heating + A2W
Heating
A2A Priority
(#5033=0)
A2A Cooling
A2W Cooling
"Same cooling Mode TDS
Control"
A2A Cooling
A2W Cycle Off (The heater just
operates without heating.)
"Cooling Operation"
A2A Heating
A2W x (Not operation)
"Heating Operation"
A2A Heating
A2W Heating
"Same heating Mode
TDS Control"
DHW Priority
(#5033=1)
Same with A2A Priority
setting
A2W Heating
A2A Cooling
"(Heating + Cooling)
TDS Control"
Same with A2A Priority
setting
Same with A2A Priority
setting
A2A : Air to Air, A2W : Air to Water
When DHW Priority is enabled, hot water (heating) operation is given priority only if the A2A & A2W
simultaneous operation is on. Other operations are the same as when A2A Priority is enabled.
How to set DHW Priority ( AE***MNYD** ) :
1. Press the " " key on the wired remote controller for 3
seconds. The setting value is changed in order of DHW
Priority ( :blink) A2A Priority ( :blink) DHW Priority
( :blink) A2A Priority ( :blink) repeatedly.
2. Setting FSV #5033 to ‘0’ becomes ‘A2A Priority’, and setting
to ‘1’ becomes ‘DHW Priority’.
How to set DHW Priority ( AE***TNWT** ) :
Press the
button, press the , or , button to select Priority A2A, and then press
the
button. Setting FSV #5033 to '0' becomes 'Priority A2A', and setting to '1' becomes
'Priority DHW'.
CAUTION
While A2W is in operation, A2A does not operate. This is a normal operation.
While A2A or A2W is not in simultaneous operation, you can use any mode without operation
mode restriction.
TDM (Time-Division Multi) Variables (TDM product Only)