Handleiding
Je bekijkt pagina 25 van 40

ENGLISH
25
English
Pipe
Pipe size
Insulation Type (Heating/Cooling)
RemarksStandard [30°C, less than 85%] High humidity [30°C, over 85%]
EPDM,NBR
Liquid
pipe
Ø6.35 ~ Ø9.52 9t 9t
Internal temperature
is higher than 120°C
Ø12.7 ~ Ø19.05 13t 13t
Gas
pipe
Ø6.35 13t 19t
Ø9.52
19t 25t
Ø12.70
Ø15.88
Ø19.05
When installing insulation in places and conditions below, use the same insulation that is used for high humidity
conditions.
<Geological condition>
- High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is cov-
ered by earth and sand.)
<Operation purpose condition>
- Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
- The ceiling frequently exposed to moisture and cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
- The place where the pipe is installed is highly humid due to the lack of ventilation system.
Bekijk gratis de handleiding van Samsung AC100NN4SEC, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Samsung |
Model | AC100NN4SEC |
Categorie | Airco |
Taal | Nederlands |
Grootte | 5338 MB |