No Error Code Meaning Remarks
24 E441
Cooling operation restricted at outdoor temperature below
Tcool_low value (default:0°C)
1. Check the range of temperature limited for cooling
operation
2. Check the outdoor temperature sensor
25 E458 Fan speed error FAN1 ERROR
26 E461 Error due to operation failure of inverter compressor -
27 E462 System stop due to full current control -
28 E463 Over current trip / PFC over current error Check OLP sensor
29 E464 IPM Over Current(O.C)
1. Check if the service valve is open
2. Check the state of refrigerant
3. Check if connecting wire and the pipe are OK
4. Check the compressor
30 E465 Comp. Over load error -
31 E466 DC-Link voltage under/over error Check AC Power and DC Link Voltage
32 E467
Error due to abnormal rotation of the compressor or
unconnected wire of compressor
Check Comp wire
33 E468 Error on current sensor (Short or Open) Check Outdoor Inverter PBA.
34 E469 Error on DC-Link voltage sensor (Short or Open) -
35 E470 Outdoor unit EEPROM Read/Write error (Option) Check Outdoor EEPROM Data
36 E471 Outdoor unit EEPROM Read/Write error (H/W) Check Outdoor EEPROM PBA
37 E474 Error on IPM Heat Sink sensor of inverter 1 (Short or Open) Check Outdoor Inverter PBA.
38 E475 Error on inverter fan 2 FAN2 ERROR
39 E483 Overvoltage of H/W detect DC link Check AC Power
40 E484 PFC Overload (Over current) Error Check Outdoor Inverter PBA.
41 E485 Error on input current sensor of inverter 1 (Short or Open) Check Outdoor EEPROM PBA
42 E488 Inverter input voltage sensor error Check Outdoor Inverter PBA
43 E500 IPM over heat error on inverter 1 Check Outdoor Inverter PBA.
44 E508 Smart install is not installed -
45 E554 Gas leak detected Check the refrigerant
46 E556 Error due to mismatching capacity of indoor and outdoor unit Check the indoor and outdoor unit capacity
47 E557 DPM remote controller option error Check the indoor option code
48 E563 Error due to mismatching indoor and outdoor unit Check the outdoor EEPROM data and indoor option code
49 E590 Inverter EEPROM Checksum error -