Installation Procedure
Installation Procedure
Main power cable specifications
The power cable is not supplied with air conditioner.
Select the power supply cable in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Model Outdoor unit Input current (A) Power supply
Indoor unit Outdoor unit Hz
Voltage range (V) Outdoor unit
Indoor
unit
Total MCA(A) MFA(A)
Rated Min. Max. Cooling Heating
AC026BNNDEH
AC026BXADEH
50 220 to 240 198 264 10.0 10.0 1.0 11.0 11.0 12.5
AC026BN1DEH 50 220 to 240 198 264 10.0 10.0 1.0 11.0 11.0 12.5
AC035BNMDEH
AC035BXADEH
50 220 to 240 198 264 10.0 10.0 2.5 12.5 12.5 13.8
AC035BNNDEH 50 220 to 240 198 264 10.0 10.0 1.0 11.0 11.0 12.5
AC035BN1DEH 50 220 to 240 198 264 10.0 10.0 1.0 11.0 11.0 12.5
AC052BN4DEH
AC052BXADEH
50 220 to 240 198 264 16.5 16.5 1.0 17.5 17.5 20.6
AC052BNMDEH 50 220 to 240 198 264 16.5 16.5 2.5 19.0 19.0 20.9
AC052BNNDEH 50 220 to 240 198 264 16.5 16.5 1.0 17.5 17.5 20.6
AC071BN4DEH
AC071BXADEH
50 220 to 240 198 264 20.0 20.0 1.5 21.5 21.5 25.0
AC071BNMDEH 50 220 to 240 198 264 20.0 20.0 2.5 22.5 22.5 25.0
AC071BN6DEH 50 220 to 240 198 264 20.0 20.0 1.0 21.0 21.0 25.0
AC100BN4DEH
AC100BXADEH
50 220 to 240 198 264 24.0 24.0 2.0 26.0 26.0 30.0
AC100BNCDEH 50 220 to 240 198 264 24.0 24.0 2.0 26.0 26.0 30.0
AC100BNMDEH 50 220 to 240 198 264 24.0 24.0 2.5 26.5 26.5 30.0
AC100BN6DEH 50 220 to 240 198 264 24.0 24.0 2.5 26.5 26.5 30.0
AC120BN4DEH
AC120BXADEH
50 220 to 240 198 264 24.0 24.0 1.2 25.2 25.2 30.0
AC120BN6DEH 50 220 to 240 198 264 24.0 24.0 1.4 25.4 25.4 30.0
AC120BNMDEH 50 220 to 240 198 264 24.0 24.0 1.9 25.9 25.9 30.0
AC120BNCDEH 50 220 to 240 198 264 24.0 24.0 1.6 25.6 25.6 30.0
Main power terminal block specifications
1-phase terminal block specifications
1(L) 2(N)
F1 F2
L N
15 12
11.4
10.1
3-phase terminal block specifications
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
9.95
11.55
10.1
11.4