Installation Procedure
Step 8 Adding refrigerant (R-32)
Precautions on adding the R-32 refrigerant
In addition to the conventional charging procedure, the
following requirements shall be kept.
• Make sure that contamination by other refrigerants does
not occur for charging.
• To minimize the amount of refrigerant, keep the hoses
and lines as short as possible.
• The cylinders shall be kept upright.
• Make sure that the refrigeration system is earthed before
charging.
• Label the system after charging, if necessary.
• Extreme care is required not to overcharge the system.
• Before recharging, the pressure shall be checked with
nitrogen blowing.
• After charging, check for leakage before commissioning.
• Be sure to check for leakage before leaving the work area.
The outdoor unit is loaded with sufficient refrigerant for
the standard piping. Thus, refrigerant must be added if the
piping is lengthened. This operation can only be performed
by a qualified refrigeration specialist. To determine the
quantity of refrigerant charge, see Calculating the quantity
of refrigerant to add on page 27
1 Check if the stop valve is closed completely.
2 Charge the refrigerant through the service port of the
liquid stop valve.
3 If you have any difficulty charging the refrigerant as
described in the steps above, take the following steps:
a Open the liquid stop valve and gas stop valve.
b Operate the air conditioner by pressing the K2 key on
the outdoor unit PCB.
c After about 30 minutes, charge the refrigerant
through the service port of the gas stop valve.
Indoor Unit
Outdoor Unit
Ref
Vacuum
pump
Liquid side stop
valve(service port)
Gas side stop
valve(service port)
Important information: regulation regarding
the refrigerant used
This product contains fluorinated greenhouse gases. Do not
vent gases into the atmosphere.
CAUTION
• Inform user if the system contains 5 tCO
2
e or more of
fluorinated greenhouse gases. In this case, it must be
checked for leakage at least once every 12 months, according
to regulation No. 517/2014. This activity must be covered by
qualified personnel only. In the case of the situation above,
the installer (or authorized person with responsibility for
final check) must provide a maintenance book, with all the
information recorded, according to REGULATION (EU) No.
517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE
COUNCIL of 16 April 2014 on fluorinated greenhouse gases.
Please fill in the following with indelible ink on the refrigerant
charge label supplied with this product and on this manual.
•
: The factory refrigerant charge of the product.
•
: The additional refrigerant amount charged in the
field.
•
+ : The total refrigerant charge.