No.
Error
Code
Meaning Remarks
20 E440
Heating operation restricted at outdoor temperature over
Theat_high value (default:30°C)
1. Check the range of temperature limited for heating
operation
2.Check the outdoor temperature sensor
21 E441
Cooling operation restricted at outdoor temperature below
Tcool_low value (default:0°C)
1. Check the range of temperature limited for cooling
operation
2.Check the outdoor temperature sensor
22 E458
Fan speed error FAN1 ERROR
23 E461
Error due to operation failure of inverter compressor -
24 E462
System stop due to full current control -
25 E463
Over current trip / PFC over current error Check OLP sensor
26 E464
IPM Over Current(O.C)
1.Check if the service valve is open
2.Check the state of refrigerant
3.Check if connecting wire and the pipe are OK
4.Check the compressor
27 E465
Comp. Over load error -
28 E466
DC-Link voltage under/over error Check AC Power and DC Link Voltage
29 E467
Error due to abnormal rotation of the compressor or
unconnected wire of compressor
Check Comp wire
30 E468
Error on current sensor (Short or Open) Check Outdoor Inverter PBA.
31 E469
Error on DC-Link voltage sensor (Short or Open) -
32 E470
Outdoor unit EEPROM Read/Write error (Option) Check Outdoor EEPROM Data
33 E471
Outdoor unit EEPROM Read/Write error (H/W) Check Outdoor EEPROM PBA
34 E474
Error on IPM Heat Sink sensor of inverter 1 (Short or Open) Check Outdoor Inverter PBA.
35 E475
Error on inverter fan 2 FAN2 ERROR
36 E483
AC Input voltage is over-voltageerror Check AC Power
37 E484
PFC Overload (Over current) Error Check Outdoor Inverter PBA.
38 E485
Error on input current sensor of inverter 1 (Short or Open) Check Outdoor EEPROM PBA
39 E488
ErroronAC Input voltage sensor (Short or Open) Check Outdoor Inverter PBA.
40 E500
IPM over heat error on inverter 1 Check Outdoor Inverter PBA.
41 E508
Smart install is not installed -
42 E554
Gas leak detected Check the refrigerant
43 E556
Error due to mismatching capacity of indoor and outdoor
unit
Check the indoor and outdoor unit capacity
44 E557
DPM remote controller option error Check the indoor option code
45 E590
Inverter EEPROM Checksum error -
46 E660
Inverter Boot Code error -