Testing operations
1. Check the power supply between the outdoor unit and the auxiliary circuit breaker.
1 phase power supply : L1, L2
2. Check the indoor unit.
1) Check that you have connected the power and communication cables correctly. (If the power cable and
communication cables one mixed up or connected incorrectly, the PCB will be damaged.)
2) Check the thermistor sensor, drain pump/hose, and display are connected correctly.
3) KEY buttons are on Main PBA of Outdoor Unit.
3. Press K2 on the outdoor unit PCB to run the test mode and stop.
K2 Mode DISPLAY
1 Cooling Test Mode
2
Inverter checker
(Load PBA inspection operation)
3 Pump down in Cool mode
4. After 12 minutes of stationary condition check each indoor unit air treatment :
Cooling mode(indoor unit check) Inlet air temp. – Outlet air temp. ≥ 18°F(reference only)
5. How to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode) :
Press [K3] button over 1 sec to reset the power supply of the outdoor unit and deactivate the eco mode (standby mode).
CAC 저온향 과제 북미향 실외기IM_EN_DB68-07245A-00.indd 32 2017-05-10 오후 2:53:11