Installation Procedure
WARNING
Because your air conditioner contains R-32 refrigerant,
make sure that it is installed, operated, and stored it
in a room whose floor area is larger than the minimum
required floor area specified in the following table:
Minimum required room area (A, m²)
m (kg) Ceiling-mounted type
1.842 No requirement
1.843 3.64
1.9 3.75
2.0 3.95
2.2 4.34
2.4 4.74
2.6 5.13
2.8 5.53
3.0 5.92
3.2 6.48
3.4 7. 32
3.6 8.20
3.8 9.14
4.0 10.1
4.2 11.2
4.4 12.3
4.6 13.4
4.8 14.6
5.0 15.8
5.2 17.1
5.4 18.6
5.6 20.0
5.8 21.5
6.0 23.0
m : Total refrigerant charge in the system
A : Minimum required floor area
IMPORTANT: it’s mandatory to consider either the
table above or taking into consideration the local law
regarding the minimum living space of the premises.
Minimum installation height of indoor unit is 2.2 m for
ceiling-mount type.
CAUTION
As a rule, the unit cannot be installed at a height of less
that 2.5m.
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C and humidity is over
80%, you must apply an extra 10mm thick polyethylene
insulation or a similar type of insulation to the body of
the indoor unit.
Do not install the air conditioner in following
places.
Place where there is mineral oil or arsenic acid. Resin
parts flame and the accessories may drop or water may
leak. The capacity of the heat exchanger may reduce or
the air conditioner may be out of order.
A place with exposure to mineral oil, oil vapour or
cooking area where there is spray (If oil adheres to the
heat exchanger, performance degradation, spray or
condensation scattering may occur. If oil adheres to a
plastic component, the component may deform or get
damaged. Such issues may result in a system failure or
refrigerant leak.)
A place with aromatic diffusers, aromatherapy, scented
candles or perfumes as the chemicals may react to the
product's materials and may result in system failure or
refrigerant leaks.
The place where corrosive gas such as sulphuric acid
gas generates from the vent pipe or air outlet.
The copper pipe or connection pipe may corrode and
refrigerant may leak.
The place where there is a machine that generates
electromagnetic waves. The air conditioner may not
operate normally due to control system.
The place where there is a danger of existing
combustible gas, carbon fibre or flammable dust.
The place where thinner or gasoline is handled.
Gas may leak and it may cause fire.
The place where is close to heat sources.
Do not use the indoor unit for preservation of food
items, plants, equipment, and art works. This may cause
deterioration of their quality.
Do not install the indoor unit if it has any drainage
problem.