Handleiding
Je bekijkt pagina 5 van 46

5
English
Safety Information
• Do not install the product in a ship or a vehicle (such as a
campervan). Salt, vibration or other environmental factor
may cause the product malfunction, electric shock or fire.
• Excessive indoor humidity or clogged condensate drain
lines may cause water to drip from indoor units. Do not
install the indoor unit where dripping could result in
damage to property, such as above electronic equipment or
other sensitive instruments.
• Our units should be installed in compliance with the
spaces shown in the installation manual, to ensure
accessibility from both sides and allow repairs or
maintenance operations to be carried out. The
unit’s components should be accessible and easy to
disassemble without endangering people and objects.
• For this reason, when provisions of the installation
manual are not complied with, the cost required to
access and repair the units (in SAFETY CONDITIONS,
as set out in prevailing regulations) with harnesses,
ladders, scaffolding or any other elevation system will
NOT be considered part of the warranty and will be
charged to the end customer.
• The local gas regulations shall be observed.
• To handle, purge, and dispose the refrigerant, or break
into the refrigerant circuit, the worker should have a
certificate from an industry-accredited authority.
• While in installation or relocation of the product, do
not mix the refrigerant with other gases including air
or unspecified refrigerant. Failure to do so may cause
pressure increase to result in rupture or injury.
• Do not cut or burn the refrigerant container or pipings.
• Installation must be carried out by qualified personnel
for handling the refrigerant. Additionally, reference the
regulations and laws.
• Be careful not to let foreign substances (lubricating oil,
refrigerant, water, etc.) enter the pipings.
• When mechanical ventilation is required, ventilation
openings shall be kept clear of obstruction.
• For disposal of the product, follow the local laws and
regulations.
• Do not work in a confined place.
• The work area shall be blocked.
• The refrigerant pipings shall be installed in the position
where there are no substances that may result in
corrosion.
• The following checks shall be performed for installation :
– The charging amount depends on the room size.
– The ventilation devices and outlets are operating
normally and are not obstructed.
– Markings and signs on the equipment shall be
visible and legible.
• Upon leakage of the refrigerant, ventilate the room.
When the leaked refrigerant is exposed to flame, it may
cause generation of toxic gases.
• Make sure that the work area is safe from flammable
substances.
• Note that the refrigerant has no odour.
• The units are not explosion proof so they must be
installed with no risk of explosion.
• This product contains fluorinated gases that contribute
to global greenhouse effect. Accordingly, do not vent
gases into the atmosphere.
• For installation with handling the refrigerant(R-32), use
dedicated tools and piping materials. Working pressure
of R-32 is higher than R410A, So failure to use the
dedicated tools and piping materials may cause rupture
or injury. Furthermore, it may cause serious accidents
such as water leakage, electric shock or fire.
• Servicing shall be performed as recommended by the
manufacturer. In case other skilled persons are joined
for servicing, it shall be carried out under supervision
of the person who is competent in handling flammable
refrigerants.
• For servicing the units containing flammable
refrigerants, safety checks are required to minimise the
risk of ignition. R-32 is slightly more flammable than
R410A hence additional precautions are required when
dealing with it.
• Servicing shall be performed following the controlled
procedure to minimize the risk of flammable
refrigerant or gases.
• Do not install where there is a risk of combustible gas
leakage.
• Do not place heat sources.
• Be cautious not to generate a spark as follows:
– Do not remove the fuses with power on.
DB68-13503A-01_IM_CAC R-32 WindFree1_4way_EA_EN_.indd 5DB68-13503A-01_IM_CAC R-32 WindFree1_4way_EA_EN_.indd 5 2025-04-08 오전 8:53:182025-04-08 오전 8:53:18
Bekijk gratis de handleiding van Samsung AC035FE1DKF, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Samsung |
Model | AC035FE1DKF |
Categorie | Airco |
Taal | Nederlands |
Grootte | 4702 MB |